A.O. Smith 184769-000 Unconfined Space, Confined Space, Water Connections, Closed Water System

Page 5

UNCONFINED SPACE

In buildings of conventional frame, brick or stone construction, unconfined spaces may provide adequate air for combustion, ventilation, and draft hood dilution.

If the unconfined space is within a building of tight construction (building using the following construction: weather stripping, heavy insulation, caulking, vapor barrier, etc.), air for combustion, ventilation, and draft hood dilution must be obtained from outdoors. The installation instructions for confined spaces must be followed.

CONFINED SPACE

When drawing combustion and dilution air from inside a conventionally constructed building to a confined space, such a space shall be provided with two permanent openings. ONE IN OR WITHIN 12 INCHES OF THE ENCLOSURE TOP AND ONE IN OR WITHIN 12 INCHES OF THE ENCLOSURE BOTTOM. Each opening shall have a free area of at least one square inch per 1000 Btuh of the total input of all appliances in the enclosure, but not less than 100 square inches.

If the confined space is within a building of tight construction, air for combustion, ventilation and draft hood dilution must be obtained from outdoors. When directly communicating with the outdoors or communicating through vertical ducts, two permanent openings, located in the above manner, shall be provided. Each opening shall have a free area of not less than one square inch per 4000 Btuh of the total input of all appliances in the enclosure. If horizontal ducts are used, each opening shall have a free area of not less than one square inch per 2000 Btuh of the total input of all appliances in the enclosure.

In calculating the free area of a vent opening, the blocking effect of screens, louvers and grills should be considered. Screens shall not be of a mesh smaller than 1/4 inch square. If the free area is not known, the latest edition of National Fuel Gas Code ANSI Z223.1 recommends using figures of 20-25 percent free area for wood louvers or 60-75 percent for metal grills or louvers.

WATER CONNECTIONS

Refer to figure 1 for typical installation. A suitable pipe thread sealant must be used to prevent leakage.

WATER (POTABLE) HEATING AND SPACE HEATING

For WATER HEATING (POTABLE) and SPACE HEATING:

1.All piping components connected to this unit for space heating applications shall be suitable for use with potable water.

2.Toxic chemicals, such as those used for boiler treatment, shall NEVER be introduced into this system.

3.This unit may NEVER be connected to any existing heating system or component(s) previously used with a non-potable water heating appliance.

4.When the system requires water for space heating at temperatures higher than required for domestic water purposes, a tempering valve must be installed. Please refer to Fig. 2 for suggested piping arrangement.

FIGURE 2

CLOSED WATER SYSTEM

A closed system will exist if a back-flow preventer (check valve), pressure reducing valve, or other similar device is installed in the cold water line between the water heater and the street main (or well). Excessive pressure may develop due to the thermal expansion of heated water causing premature tank failure or intermittent relief valve operation. This type of failure is not covered by the limited warranty. An expansion tank may be necessary in the cold water supply to alleviate this situation, see fig. 1. Contact the local plumbing authority.

If the temperature and pressure relief valve on the appliance discharges periodically, this may be due to thermal expansion in a closed water supply system. Contact the water supplier or local plumbing inspector on how to correct this situation. Do not plug the temperature and pressure relief valve.

GAS CONNECTIONS

The minimum gas supply pressure for input adjustment is 5.0" W.C. for natural gas (11.0" W.C. for propane).

THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER THAN 10.5"-NATURAL, 13.0"-PROPANE WATER COLUMN (1/2 POUND PER SQUARE INCH [3.5 kPa]) SUPPLY PRESSURE. EXPOSURE TO HIGHER GAS SUPPLY PRESSURE MAY CAUSE DAMAGE TO THE CONTROL WHICH COULD RESULT IN FIRE OR EXPLOSION. If overpressure has occurred such as through improper testing of gas lines or emergency malfunction of the supply system, the control must be checked for safe operation. Make sure that the outside vents on the supply regulators and the safety vent valves are protected against blockage. These are parts of the gas supply system, not the heater. Vent blockage may occur during ice storms.

IT IS IMPORTANT TO GUARD AGAINST CONTROL FOULING FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.

All piping must comply with local codes and ordinances or with the National Fuel Gas Code (ANSI Z223.1/NFPA-54) whichever applies. Copper and brass tubing and fittings (except tin lined copper tubing) shall not be used.

REFER TO FIG. 1 FOR CONNECTION DETAILS. BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS PIPE IS CLEAN ON THE INSIDE.

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED DRIP LEG) MUST BE INCORPORATED IN THE PIPING, FIG. 1. The dirt leg must be readily accessible. Install in accordance with

5

Image 5
Contents GAS GET to Know Your Water Heater Replacement Parts and Deliming ProductsInstall in Accordance with Local Codes General Safety Information Required Ability InstallationGeneral Location of HeaterConfined Space Unconfined SpaceWater Connections Water Potable Heating and Space HeatingOperation Not Force What to do if YOU Smell GASDraft Hood Operation High Altitude InstallationTemperature Regulation Maintenance Problem Cause Solution TroubleshootingService and Labor Responsibility Warranty Periods ModelClaim Procedure Installation InformationReplacement Parts

184769-000 specifications

A.O. Smith 184769-000 is a notable water heater model that epitomizes efficiency and reliability in the realm of home appliances. As part of A.O. Smith’s comprehensive line of water heating solutions, this product showcases cutting-edge technologies and features that cater to contemporary household demands.

One of the standout characteristics of the A.O. Smith 184769-000 is its impressive energy efficiency. It is designed to minimize energy consumption while maximizing performance. The unit utilizes advanced insulation technology that reduces heat loss, ensuring that the water maintains its temperature even when the heater is not in active use. This feature not only contributes to lower energy bills but also promotes sustainability by reducing the carbon footprint associated with energy production.

The A.O. Smith 184769-000 incorporates high-quality components that guarantee long-lasting durability. The tank is crafted from robust materials that resist rust and corrosion, extending the life of the appliance. Coupled with the manufacturer’s industry-leading warranty, homeowners can enjoy peace of mind with the knowledge that they are investing in a product built to last.

In terms of capacity, this model offers various sizes to suit the needs of different households, whether for small families or larger homes. The water heater provides sufficient hot water supply to meet daily needs, from showering and cooking to laundry and dishwashing.

Another significant feature of the A.O. Smith 184769-000 is its intuitive digital interface. Users can easily adjust settings, monitor performance, and receive alerts for maintenance or issues through this user-friendly display. This technology allows for better control over the heating process, ensuring that households can enjoy hot water when they need it most.

The safety features integrated into the A.O. Smith 184769-000 are also commendable. It includes sophisticated over-temperature protection and a pressure relief valve, safeguarding the unit's operation and preventing potential hazards.

In summary, the A.O. Smith 184769-000 stands out for its energy efficiency, durable construction, user-friendly digital controls, and robust safety features. These characteristics make it a reliable choice for any homeowner looking to enhance their hot water supply system. Whether upgrading an existing unit or installing a new water heater, this model is engineered to meet and exceed expectations.