Aurora of America Horizontal Split Case & Split Case Fire Pump, 492, 442 manual Pump Assembly

Page 20

MAINTENANCE (continued)

PAGE 17

 

 

 

7. PUMP ASSEMBLY (continued)

CAUTION: BE SURE BEARING HOUSING/CASING MATING SURFACES ARE CLEAN AND FREE FROM BURRS, AS THIS WILL AFFECT THE ALIGNMENT OF THE ROTOR/CASING.

L.Attach the bearing cartridges to the lower casing using the appropriate dowel pins (158B).

M.Inspect the upper casing (3) to assure that the water passage is clean and free from foreign material. Apply a light coat of grease to the upper and lower casing mating surfaces and install a new casing gasket (157) on the lower casing, making sure the holes are aligned. Position the pins in the casing wearing rings to align with the slots in the lower casing. Lower the upper casing into position. Install the casing alignment pins and securely bolt the upper and lower casing together using the capscrews.

N.Install the packing (212), lantern rings (10), split glands (19) and gland nuts.

The pump assembly is now complete except for packing adjustment, which should be accomplished after the pump is installed, primed and started up. Refer to the maintenance section of this manual for specific packing adjustment instructions.

Image 20
Contents Split Case Fire Pump ForTable of Contents Page Pump Identification Pump Identification442 & 492 Split Case Pumps DriverStorage of Pumps and Caution Notes Introduction and Installation InstallationIntroduction GeneralBaseplate Installation Minimum Submergence of Suction Pipe and PIT DesignLocation and Handling FoundationGrouting PipingAuxiliary Piping Connections and Gauges Final Coupling AlignmentRotation Coupling AlignmentFlexible Shafting Alignment Mechanical Seals Typical Mechanical SealPriming OperationOperating AT Reduced Capacity Starting the Pump Bearing Operating TemperatureTroubleshooting Operating Problems Maintenance Maintenance HistoryAction Required Frequency Hours of Operation Inspections and Preventive Maintenance RequirementsBearing Lubrication Packing Replacement Packing BOXPump Disassembly Pump Model Pump SizeGloves Must be Worn When Handling Heated Parts Pump Assembly Pump Assembly Pump Assembly Returning Parts Repair PartsOrdering Parts Page Page Page Sectional Drawing Standard ConstructionSectional Drawings Description