Harbor Freight Tools R-410A manual Cooling Full Load

Page 23

GTC48S1 Matched with GTADP-4860-C (HE49948D210B2705AW) -A Coils

Full Load Capacities based upon rated flow of 12 GPM of 15% methanol/mass at 1500 CFM airflow.

COOLING FULL LOAD

Entering

Entering

Total

Sensible

Sensible

Power

Heat of

 

Fluid

Air Temp.

Capacity

Capacity

to Total

Input

Rejection

EER

Temp. (°F)

(°F)

(MBtuH)

(MBtuH)

Ratio

(KW)

(MBtuH)

 

50°

 

48.2

38.0

0.79

1.85

54.5

26.1

 

 

 

 

 

 

 

 

60°

 

46.7

36.6

0.78

2.26

54.4

20.7

 

 

 

 

 

 

 

 

70°

70° DB

45.2

35.2

0.78

2.67

54.3

16.9

 

 

 

 

 

 

 

80°

43.7

33.7

0.77

3.08

54.2

14.2

59° WB

 

 

 

 

 

 

 

90°

42.2

32.3

0.77

3.50

54.1

12.1

 

100°

 

40.7

30.9

0.76

3.91

54.0

10.4

110°

 

39.2

29.5

0.75

4.32

53.9

9.1

50°

 

51.8

39.6

0.76

1.86

58.2

27.9

 

 

 

 

 

 

 

 

60°

 

50.2

38.1

0.76

2.28

58.0

22.0

 

 

 

 

 

 

 

 

70°

75° DB

48.6

36.6

0.75

2.70

57.8

18.0

 

 

 

 

 

 

 

80°

47.0

35.1

0.75

3.13

57.7

15.0

63° WB

90°

45.4

33.6

0.74

3.55

57.5

12.8

 

 

 

 

 

 

 

 

 

100°

 

43.8

32.2

0.73

3.97

57.3

11.0

 

 

 

 

 

 

 

 

110°

 

42.2

30.7

0.73

4.40

57.2

9.6

50°

 

55.7

41.1

0.74

1.89

62.1

29.4

 

 

 

 

 

 

 

 

60°

 

53.9

39.5

0.73

2.32

61.8

23.3

 

 

 

 

 

 

 

 

70°

80° DB

52.2

38.0

0.73

2.74

61.6

19.1

80°

50.5

36.5

0.72

3.16

61.3

16.0

67° WB

 

 

 

 

 

 

 

90°

 

48.7

34.9

0.72

3.59

61.0

13.6

 

 

 

 

 

 

 

 

100°

 

47.0

33.4

0.71

4.01

60.7

11.7

 

 

 

 

 

 

 

 

110°

 

45.3

31.8

0.70

4.43

60.4

10.2

50°

 

59.7

42.5

0.71

1.92

66.2

31.1

60°

 

57.8

40.9

0.71

2.35

65.8

24.6

70°

85° DB

55.9

39.3

0.70

2.78

65.4

20.1

 

 

 

 

 

 

 

80°

54.1

37.7

0.70

3.21

65.0

16.9

71° WB

 

 

 

 

 

 

 

90°

52.2

36.1

0.69

3.64

64.7

14.4

 

 

 

 

 

 

 

 

 

100°

 

50.4

34.5

0.69

4.07

64.3

12.4

 

 

 

 

 

 

 

 

110°

 

48.5

32.9

0.68

4.50

63.9

10.8

HEATING FULL LOAD

Entering

Entering

Total

Leaving

Power

Heat of

 

Fluid

Air

Capacity

Air

Input

Absorption

COP

Temp.

Temp.

Temp. (°F)

(°F)

(MBtuH)

(°F)

(KW)

(MBtuH)

 

 

 

 

 

 

25°

 

34.1

86.1

2.93

23.8

3.4

 

 

 

 

 

 

 

30°

 

37.2

88.0

3.04

26.5

3.6

 

 

 

 

 

 

 

40°

 

43.5

91.8

3.24

32.1

3.9

 

65°

 

 

 

 

 

50°

49.7

95.7

3.44

37.6

4.2

 

 

 

 

 

 

 

60°

 

56.0

99.5

3.64

43.2

4.5

 

 

 

 

 

 

 

70°

 

62.2

103.4

3.85

48.7

4.7

 

 

 

 

 

 

 

80°

 

68.4

107.2

4.05

54.3

5.0

25°

 

33.4

90.6

3.01

23.1

3.3

 

 

 

 

 

 

 

30°

 

36.4

92.5

3.12

25.8

3.4

 

 

 

 

 

 

 

40°

 

42.5

96.2

3.33

31.2

3.7

 

 

 

 

 

 

 

50°

70°

48.6

100.0

3.53

36.5

4.0

 

 

 

 

 

 

 

60°

 

54.7

103.8

3.741

41.9

4.3

 

 

 

 

 

 

 

70°

 

60.8

107.5

3.95

47.3

4.5

 

 

 

 

 

 

 

80°

 

66.9

111.3

4.16

52.7

4.8

 

 

 

 

 

 

 

25°

 

33.7

95.8

3.38

22.4

2.9

 

 

 

 

 

 

 

30°

 

36.8

97.7

3.50

25.0

3.1

 

 

 

 

 

 

 

40°

 

43.0

101.5

3.73

30.2

3.4

 

 

 

 

 

 

 

50°

75°

49.1

105.3

3.97

35.4

3.6

 

 

 

 

 

 

 

60°

 

55.3

109.1

4.20

40.7

3.8

 

 

 

 

 

 

 

70°

 

61.5

112.9

4.43

45.9

4.1

 

 

 

 

 

 

 

80°

 

67.6

116.8

4.67

51.1

4.3

Part Load Capacities based upon rated flow of 12 GPM of 15% methanol/mass at 1075 CFM airflow.

COOLING PART LOAD

Entering

Entering

Total

Sensible

Sensible

Power

Heat of

 

Fluid

Air Temp.

Capacity

Capacity

to Total

Input

Rejection

EER

Temp. (°F)

(°F)

(MBtuH)

(MBtuH)

Ratio

(KW)

(MBtuH)

 

50°

 

35.0

28.8

0.82

1.01

38.5

34.6

 

 

 

 

 

 

 

 

60°

 

33.8

27.9

0.82

1.33

38.4

25.3

70°

70° DB

32.6

26.9

0.83

1.66

38.3

19.7

 

 

 

 

 

 

 

80°

31.5

26.0

0.83

1.98

38.2

15.9

59° WB

 

 

 

 

 

 

 

90°

30.3

25.1

0.83

2.30

38.1

13.2

 

 

 

 

 

 

 

 

 

100°

 

29.1

24.2

0.83

2.62

38.0

11.1

 

 

 

 

 

 

 

 

110°

 

27.9

23.2

0.83

2.95

38.0

9.5

50°

 

37.7

30.0

0.80

1.02

41.1

37.0

60°

 

36.4

29.0

0.80

1.35

41.0

27.0

 

 

 

 

 

 

 

 

70°

75° DB

35.1

28.0

0.80

1.68

40.8

20.9

 

 

 

 

 

 

 

80°

33.8

27.1

0.80

2.01

40.7

16.9

63° WB

 

 

 

 

 

 

 

90°

32.6

26.1

0.80

2.34

40.5

13.9

 

 

 

 

 

 

 

 

 

100°

 

31.3

25.2

0.80

2.67

40.4

11.7

110°

 

30.0

24.2

0.81

3.00

40.3

10.0

50°

 

40.4

31.1

0.77

1.04

44.0

28.6

 

 

 

 

 

 

 

 

60°

 

39.1

30.1

0.77

1.37

43.7

25.4

 

 

 

 

 

 

 

 

70°

80° DB

37.7

29.1

0.77

1.70

43.5

22.2

 

 

 

 

 

 

 

80°

36.3

28.1

0.77

2.03

43.3

18.9

67° WB

 

 

 

 

 

 

 

90°

35.0

27.1

0.78

2.36

43.0

15.7

 

100°

 

33.6

26.1

0.78

2.69

42.8

12.5

110°

 

32.2

25.1

0.78

3.02

42.5

9.2

50°

 

43.3

32.2

0.74

1.05

46.9

41.1

 

 

 

 

 

 

 

 

60°

 

41.9

31.2

0.74

1.39

46.6

30.1

 

 

 

 

 

 

 

 

70°

85° DB

40.4

30.1

0.75

1.72

46.3

23.4

 

 

 

 

 

 

 

80°

38.9

29.1

0.75

2.06

46.0

18.9

71° WB

90°

37.5

28.1

0.75

2.40

45.7

15.6

 

 

 

 

 

 

 

 

 

100°

 

36.0

27.0

0.75

2.73

45.3

13.2

 

 

 

 

 

 

 

 

110°

 

34.5

26.0

0.75

3.07

45.0

11.3

HEATING PART LOAD

Entering

Entering

Total

Leaving

Power

Heat of

 

Fluid

Air

Capacity

Air

Input

Absorption

COP

Temp.

Temp.

Temp. (°F)

(°F)

(MBtuH)

(°F)

(KW)

(MBtuH)

 

 

 

 

 

 

25°

 

23.8

85.5

2.17

16.1

3.2

 

 

 

 

 

 

 

30°

 

26.3

87.7

2.21

18.5

3.5

 

 

 

 

 

 

 

40°

 

31.3

92.0

2.28

23.3

4.0

 

65°

 

 

 

 

 

50°

36.3

96.3

2.35

28.1

4.5

 

 

 

 

 

 

 

60°

 

41.4

100.6

2.43

32.9

5.0

 

 

 

 

 

 

 

70°

 

46.4

104.9

2.50

37.7

5.4

 

 

 

 

 

 

 

80°

 

51.4

109.2

2.57

42.4

5.9

 

 

 

 

 

 

 

25°

 

23.3

90.0

2.23

15.7

3.1

 

 

 

 

 

 

 

30°

 

25.7

92.2

2.27

18.0

3.3

 

 

 

 

 

 

 

40°

 

30.6

96.4

2.34

22.6

3.8

 

 

 

 

 

 

 

50°

70°

35.5

100.6

2.42

27.3

4.3

 

 

 

 

 

 

 

60°

 

40.4

104.8

2.49

31.9

4.7

 

 

 

 

 

 

 

70°

 

45.3

109.0

2.57

36.6

5.2

 

 

 

 

 

 

 

80°

 

50.2

113.3

2.64

41.2

5.6

25°

 

23.5

95.3

2.51

15.2

2.8

 

 

 

 

 

 

 

30°

 

26.0

97.4

2.55

17.4

3.0

 

 

 

 

 

 

 

40°

 

31.0

101.7

2.63

22.0

3.4

 

 

 

 

 

 

 

50°

75°

35.9

105.9

2.71

26.5

3.9

 

 

 

 

 

 

 

60°

 

40.9

110.2

2.80

31.0

4.3

 

 

 

 

 

 

 

70°

 

45.8

114.5

2.88

35.5

4.7

 

 

 

 

 

 

 

80°

 

50.8

118.7

2.97

40.0

5.0

Form No.

S3423-1112

Supersedes

S3423-912

Page

23 of 28

Image 23
Contents Engineered Features Cross-Reference Table Shipping Weights GT SeriesShipping Weights Fossil Fuel Coils Airflow Corrections Indoor Blower Performance Rated CFMApproved Compressor and GTA-Coil Approved Compressor, GTA-Coil & Blower Section CombinationsRatings Based on Approved Compressor & GTA-Coil Only Correction Factors @ Increased Water Flows For Use with Gas or Oil Furnace as Dual Fuel InstallationRatings Based on Approved Compressor and Fossil Fuel A-Coil Refrigerant Connections Self-Sealing Fittings Side Filter Rack For Upflow InstallationsOptional Field Installed Start Kits for 1-Phase Models Optional Field Installed Start Kit for 1-Phase ModelsGround Loop Service Accessories Ground Loop AccessoriesGround Water/Water Loop Service Accessories Ground Water/Water Loop AccessoriesEvaporator and Blower in Horizontal Position Drain pan kit Model GTHZ-1 TOP Upflow Position Filter Application Table Counterflow Filter Application for All Installation PositionsCooling Full Load GTC36S1 Matched with GTA3600UD1-A CoilTotal GTC48S1 Matched with GTA4860UD1-A Coil GTC48S1 Matched with GTA4860UD1-A Coil GTC60S1 Matched with GTA4860UD1-A Coil GTC60S1 Matched with GTA4860UD1-A Coil Power Heat Total Leaving Power Heat Cooling Full Load Cooling Full Load Total Leaving Total Leaving Power Heat Overflow Main Drain Fossil Fuel ADP Coil Section DimensionsGTA Coil Dimensions If Used Without Cabinet GTA Coil Dimensions if Used Without Cabinet

R-410A specifications

Harbor Freight Tools R-410A is a high-quality refrigerant that has become essential for modern air conditioning systems. Designed specifically for use in HVAC applications, R-410A is a hydrofluorocarbon (HFC) refrigerant that plays a crucial role in energy efficiency and improved environmental performance. One of its standout characteristics is its ability to operate at a higher pressure than older refrigerants like R-22, making it an ideal choice for new systems and retrofits.

One of the main features of Harbor Freight Tools R-410A is its excellent thermodynamic properties, which contribute to improved cooling efficiency. The refrigerant boasts a high latent heat of vaporization, allowing it to absorb and release significant amounts of heat during the compression and evaporation processes. This efficiency translates to lower operational costs and reduced energy consumption, making it a popular choice for environmentally conscious consumers and businesses alike.

In terms of safety, R-410A is non-toxic and non-flammable, addressing concerns associated with certain older refrigerants. This aspect is particularly important in residential and commercial settings, where the safety of occupants is paramount. Furthermore, R-410A has a zero ozone depletion potential (ODP), aligning with global initiatives to phase out substances that are harmful to the atmosphere.

Harbor Freight Tools R-410A is also compatible with various lubricants and doesn't require the use of mineral oil, which is essential when retrofitting older systems. The refrigerant’s unique blend allows for seamless operation in systems designed to operate at high efficiency.

With a boiling point of approximately -51 degrees Celsius, R-410A works effectively in a wide temperature range, making it suitable for various cooling and heating applications. This versatility ensures that users can rely on this refrigerant for both residential air conditioning units and commercial systems alike.

Overall, Harbor Freight Tools R-410A stands out as a modern solution for HVAC needs, combining efficiency, safety, and environmental responsibility. Its innovative characteristics and features make it a go-to choice for both contractors and DIY enthusiasts looking to optimize their air conditioning systems while adhering to current environmental standards. The continued adoption of R-410A underscores the ongoing evolution of the HVAC industry, catering to the needs of a more eco-conscious market.