Mitsubishi Electronics MUY-D36NA, MUZ-D36NA, U1 Check of outdoor fan motor, Check of power supply

Page 31

Fan motor does not operate or stops operating shortly after starting the operation.

D Check of outdoor fan motor

Check the connection between the connector CN931 and CN932.

Is the resistance between each ter-

minal of outdoor fan motor normal? Yes (Refer to 10-4.)

No

(Fixed to either 5 or 0 VDC) No

No

Replace the outdoor DC fan motor.

Disconnect CN932 from outdoor electronic control P.C. board, and turn on the power supply.

Rotate the outdoor fan motor manually and measure the voltage of CN931.

Between 1(+) and 5(-)

Between 2(+) and 5(-)

Between 3(+) and 5(-)

Does the voltage between each terminal become 5 VDC and 0 VDC repeatedly?

Yes

Does the outdoor fan motor rotate smoothly?

Yes

Replace the outdoor electronic control P.C. board.

Outdoor unit does not operate.

E Check of power supply

Check the connecting of parts of main power supply circuit.

Turn ON power supply.

Is there voltage of 208 / 230 VAC in the power supply terminal block?

Yes

Is the output voltage from the noise filter P.C. board 208 / 230 VAC?

Yes

Is the input voltage to the power board 208 / 230 VAC?

Yes

 

 

Check the power supply cable.

No

 

 

 

Replace the noise filter P.C. board.

No

 

 

 

Replace the reactor.

No

 

Is the input voltage to the outdoor electronic

 

 

 

 

 

Replace the power board.

control P.C. board 294 / 325 VDC?

No

 

 

Yes

 

 

 

 

 

 

 

 

Replace the outdoor electronic control P.C. board.

31

Image 31 Contents
Outdoor Unit Page Part Names and Functions Technical ChangesTNB220FMCHT TotalHspf COPARI Operating RangeSeer Required Space Outlines and DimensionsWiring Diagram MUY-D30NA MUY-D36NA LEV Refrigerant System DiagramMAX. Refrigerant Piping Length and MAX. Height Difference Performance Data Cooling Capacity DataHeating Performance Curve CoolingMUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NACondensing Pressure Cooling 380 420 340 300 26068 100 105F MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA Standard Operation DataInput correction factors Test RUN Operation How to operate fixed-frequency operation Relation between main sensor and actuator Actuator ControlOutdoor FAN Motor Control R.V. Coil Control MUZChange in Defrost Setting Service FunctionsPRE-HEAT Control Take care of the following during servicing TroubleshootingFailure Mode Recall Function Operational procedure Outdoor unit failure mode table LED LED1 LED2 Troubleshooting Check TableMUZ YLW BRN BLK WHT WHT REDTroubleshooting Flow How to check inverter/ compressorCheck of outdoor thermistors Heating operation does not work Check of R.V. coil MUZ-D30/36Check of outdoor fan motor Check of power supplyCheck of LEV Check of compressor start failureHow to check miswiring and serial signal error Check of HPS Electromagnetic noise enters into TV sets or radios Outdoor electronic control P.C. board Test Point Diagram and VoltageNoise filter P.C. board CN5 Outdoor power boardCN2 CN3Removing the cabinet Photo Disassembly InstructionsRemoving R.V. coil MUZ Photo 5 Inverter assemblyHPS MUZ Temperature thermistor and ambient temperatureThermistor Removing outdoor fan motorRemoving the reactor Removing the compressor and 4-way valve PhotoPage Specifications subject to change without notice