Mitsubishi Electronics MUZ-D36NA, MUY-D36NA, U1, MUZ-D30NA Troubleshooting Check Table, LED1 LED2

Page 25

10-3. TROUBLESHOOTING CHECK TABLE

MUZ-D30NA MUZ-D36NA MUY-D30NA MUY-D36NA

No.

Symptom

Indication

Abnormal point / Condition

Condition

 

Correspondence

LED1

LED2

 

 

 

(Red)

(Yellow)

 

 

 

 

 

 

 

 

 

IPM protection stop or lock protection stop is continuously

• Check the connection of the compressor connect-

 

 

 

 

 

ing wire.

 

 

 

 

 

 

performed three times within 1 minute after the compressor

"How to check inverter/compres-

1

 

Lightning

Twice

Outdoor power system

• Refer to 10-5.

 

gets started, or converter protection stop or bus-bar voltage

 

sor".

 

 

 

 

 

 

protection stop is continuously performed 3 times within 3

 

 

 

 

 

 

• Refer to 10-5.

"Check of compressor start failure".

 

 

 

 

 

minutes after start-up.

 

 

 

 

 

• Check the stop valve.

 

 

 

 

 

 

2

 

Lightning

3 times

Discharge temperature therm-

A short circuit is detected in the thermistor during opera-

• Refer to 10-5.

"Check of outdoor thermistor".

 

istor

tion, or an open circuit is detected in the thermistor after 10

 

 

 

 

minutes of compressor start-up.

 

 

 

 

 

 

 

 

 

3

 

Lightning

4 times

Fin temperature thermistor

A short or open circuit is detected in the thermistor during

• Refer to 10-5.

"Check of outdoor thermistor".

 

P.C. board temperature therm-

 

 

 

operation.

• Replace the outdoor electronic control P.C. board.

 

 

 

 

istor

 

 

 

 

 

 

 

Ambient temperature thermis-

A short or open circuit is detected in the thermistor during

 

 

 

Outdoor

 

 

tor

operation.

 

 

 

 

 

 

A short circuit is detected in the thermistor during operation,

 

 

 

unit does

 

 

Outdoor heat exchanger

 

 

 

 

 

or an open circuit is detected in the thermistor after 5 minutes

 

 

4

not oper-

Lightning

5 times

• Refer to 10-5.

"Check of outdoor thermistor".

temperature thermistor

(in cooling) and 10 minutes (in heating (MUZ)) of compressor

ate.

 

 

 

 

start-up.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A short circuit is detected in the thermistor during operation,

 

 

 

 

 

 

Defrost thermistor (MUZ)

or an open circuit is detected in the thermistor after 5 minutes

 

 

 

 

 

 

 

of compressor start-up.

 

 

5

 

Lightning

6 times

Serial signal

The communication fails between the indoor and outdoor unit

• Refer to 10-5.

"How to check miswiring and serial

 

for 3 minutes.

signal error.

 

 

 

 

 

 

 

6

 

Lightning

7 times

Nonvolatile memory data

The nonvolatile memory data cannot be read properly.

• Replace the outdoor electronic control P.C. board.

7

 

Lightning

8 times

Current sensor

Current sensor protection stop is continuously performed

• Replace the power board.

 

twice.

 

 

 

 

 

 

 

8

 

Lightning

11 times

Communication error between

The communication protection stop between boards is con-

• Check the connecting wire between outdoor elec-

 

P.C. boards

tinuously performed twice.

tronic control P.C. board and power board.

 

 

 

 

9

 

Lightning

12 times

Zero cross detecting circuit

The protection stop of the zero cross detecting circuit is

• Check the connecting wire among outdoor elec-

 

tronic control P.C. board, noise filter P.C. board and

 

continuously performed 10 times.

 

 

 

 

 

power board.

 

 

 

 

 

 

 

 

 

 

 

 

IPM protection

Overcurrent is detected after 30 minutes of compressor start-

• Reconnect compressor connector.

 

 

 

 

up.

• Refer to 10-5.

"How to check inverter/compres-

 

 

 

 

 

10

 

Twice

Goes out

 

 

sor".

 

 

Lock protection

Overcurrent is detected within 30 minutes of compressor

• Refer to 10-5.

"Check of compressor start failure".

 

 

 

 

 

 

 

 

start-up

• Check the stop valve.

 

 

 

 

 

 

 

 

 

 

 

• Check the power module (PAM module).

 

 

 

 

Discharge temperature protec-

Temperature of discharge temperature thermistor exceeds

 

 

11

 

3 times

Goes out

241 °F (116 °C), compressor stops. Compressor can restart

• Check the amount of gas and refrigerant circuit.

 

 

 

 

tion

if discharge temperature thermistor reads 212 °F (100 °C) or

• Refer to 10-5.

"Check of LEV".

 

 

 

 

 

less 3 minutes later.

 

 

12

 

4 times

Goes out

Fin temperature protection

The fin temperature exceeds 189 °F (87 °C) during operation.

• Check refrigerant circuit and refrigerant amount.

 

P.C. board temperature pro-

The P.C. board temperature exceeds 158 °F (70 °C) during

 

• Refer to 10-5.

"Check of LEV".

 

 

 

 

tection

operation.

 

 

 

 

 

 

13

'Outdoor

5 times

Goes out

High-pressure protection

The outdoor heat exchanger temperature exceeds 158 °F (70

• Check around of gas and the refrigerant circuit.

unit stops

°C) during cooling or indoor gas pipe temperature exceeds

• Check of stop valve.

 

 

 

 

158 °F (70 °C) during heating (MUZ).

 

and restarts

 

 

 

 

 

14

3 minutes

8 times

Goes out

Converter protection

A failure is detected in the operation of the converter during

• Replace the power board.

later' is

operation.

 

 

 

 

 

 

 

repeated.

 

 

Bus-bar voltage protection (1)

The bus-bar voltage exceeds 400 V or falls to 200 V or below

 

 

15

 

9 times

Goes out

 

during compressor operating.

• Replace the power board.

 

Bus-bar voltage protection (2)

The bus-bar voltage exceeds 400 V or falls to 50 V or below

 

 

 

 

 

 

 

 

 

 

 

during compressor operating.

 

 

16

 

13 times

Goes out

Outdoor fan motor

Failure occurs continuously three times within 30 seconds

• Refer to 10-5.

"Check of outdoor fan motor".

 

after the fan gets started.

 

 

 

 

 

 

 

17

 

Lighting

8 times

Current sensor protection

A short or open circuit is detected in the current sensor during

• Replace the power board.

 

 

 

 

 

compressor operating.

 

 

18

 

Lighting

11 times

Communication between P.C.

Communication error occurs between the outdoor electronic

• Check the connecting wire between outdoor elec-

 

control P.C. board and power board for more than 10 sec-

 

boards protection

tronic control P.C. board and power board.

 

 

 

 

onds.

 

 

 

 

 

 

 

19

 

Lighting

12 times

Zero cross detecting circuit

Zero cross signal cannot be detected while the compressor is

• Check the connecting wire among outdoor elec-

 

protection

operating.

tronic control P.C. board, noise filter P.C. board and

 

 

 

 

power board.

 

 

 

 

 

 

 

 

NOTE 1. The location of LED is illustrated at the right figure. Refer to 10-6.1. 2. LED is lighted during normal operation.

Outdoor electronic control P.C. board(Parts side)

LED2 LED1

ON

OFF

2.5-second OFF

Lighting

0.5-second ON

0.5-second ON

2.5-second OFF

The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the flashing frequency is “2”.

25

Image 25
Contents Outdoor Unit Page Part Names and Functions Technical ChangesHspf TotalCOP TNB220FMCHTARI Operating RangeSeer Required Space Outlines and DimensionsWiring Diagram MUY-D30NA MUY-D36NA LEV Refrigerant System DiagramMAX. Refrigerant Piping Length and MAX. Height Difference Performance Data Cooling Capacity DataMUZ-D30NA MUZ-D36NA MUY-D30NA Performance Curve CoolingMUY-D36NA HeatingCondensing Pressure Cooling 380 420 340 300 26068 100 105F MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA Standard Operation DataInput correction factors Test RUN Operation How to operate fixed-frequency operation Outdoor FAN Motor Control Actuator ControlR.V. Coil Control MUZ Relation between main sensor and actuatorChange in Defrost Setting Service FunctionsPRE-HEAT Control Take care of the following during servicing TroubleshootingFailure Mode Recall Function Operational procedure Outdoor unit failure mode table LED LED1 LED2 Troubleshooting Check TableMUZ YLW BRN BLK WHT WHT REDTroubleshooting Flow How to check inverter/ compressorCheck of outdoor thermistors Heating operation does not work Check of R.V. coil MUZ-D30/36Check of outdoor fan motor Check of power supplyCheck of LEV Check of compressor start failureHow to check miswiring and serial signal error Check of HPS Electromagnetic noise enters into TV sets or radios Outdoor electronic control P.C. board Test Point Diagram and VoltageNoise filter P.C. board CN2 Outdoor power boardCN3 CN5Removing the cabinet Photo Disassembly InstructionsRemoving R.V. coil MUZ Photo 5 Inverter assemblyHPS Thermistor Temperature thermistor and ambient temperatureRemoving outdoor fan motor MUZRemoving the reactor Removing the compressor and 4-way valve PhotoPage Specifications subject to change without notice

MUY-D36NA, MUZ-D30NA, U1, MUY-D30NA, MUZ-D36NA specifications

Mitsubishi Electronics has long been at the forefront of innovation in heating and cooling solutions, and its latest lineup of multi-zone air conditioning units—MUZ-D36NA, MUY-D30NA, U1, MUZ-D30NA, and MUY-D36NA—reflects this commitment to quality and efficiency. Designed for both residential and commercial applications, these units offer advanced features that enhance comfort and energy savings.

One of the standout characteristics of these models is their energy efficiency. Each unit is equipped with high SEER (Seasonal Energy Efficiency Ratio) ratings, making them ideal for users looking to reduce energy consumption while maintaining optimal indoor climates. The efficiency is complemented by inverter technology, which allows the compressor to adjust its speed based on the cooling demand. This results in a smoother operation, reduced noise levels, and significant energy savings over time.

These units also feature advanced filtration systems that improve indoor air quality. The included high-performance air filters capture dust, allergens, and other particles, ensuring that occupants breathe cleaner air. Additionally, some models are equipped with a plasma filtration system that actively neutralizes odors and airborne contaminants, making them particularly suitable for allergy sufferers.

Mitsubishi's advanced climate control technologies set these models apart. The system can be easily controlled using a user-friendly remote or via a mobile app, offering convenience and flexibility. The intelligent temperature control ensures that rooms are heated or cooled consistently, regardless of external conditions.

Installation versatility is another highlight. These units can be configured for multi-zone systems, allowing for tailored comfort in different spaces. The compact and sleek design makes them suitable for various installations, whether in homes, offices, or retail environments.

Furthermore, the MUZ-D and MUY-D series are equipped with quiet operation features, ensuring minimal disruption in both residential and commercial settings. This is particularly beneficial in spaces where noise could be a concern, such as bedrooms or conference rooms.

In summary, Mitsubishi's MUZ-D36NA, MUY-D30NA, U1, MUZ-D30NA, and MUY-D36NA offer a powerful combination of energy efficiency, advanced filtration, intelligent controls, and quiet operation. These features make them an excellent choice for anyone looking to enhance indoor comfort while minimizing environmental impact. Whether it's for a single room or an entire building, these units are engineered to deliver reliable performance year-round.