F Check of compressor start failure
Confirm that 1~4 is normal. •Electrical circuit check
1.Contact of lead wire leading to compressor
2.Output voltage of the outdoor electronic control P.C. board and balance of them (See
3.Direct current voltage to the outdoor electronic control P.C. board
4.Voltage between outdoor terminal block
Does the compressor run for 10 seconds or more after it starts?
No
After the compressor is heated with a drier, does the compressor start? 1
Yes
|
| Check the refrigerant circuit. | |
Yes |
| Check the stop valve. | |
|
|
| |
|
| Replace the compressor. | |
No | |||
|
Compressor start failure. Activate
1
Heat the compressor with
a drier for about 20 minutes. Do not recover refrigerant gas while heating.
Heating part
When cooling, heat exchanger of
G Check of LEV
Turn ON power supply to the outdoor unit after checking LEV coil is mounted to the LEV body securely.
Is "click - click" sound heard?
Or, do you feel vibration of the LEV coil with a hand? No
Disconnect the connector CN795.
Is there normal resistance to LEV coil?
No
Replace the LEV coil.
|
| Normal | |
Yes | |||
|
|
| Replace the outdoor electronic |
Yes |
| control P.C. board. |
32