Mitsubishi Electronics MUZ-GE18NA, MUY-GE12NA Performance Curve Cooling, MUZ-GE09NA MUY-GE09NA

Page 14

2)COOLING CAPACITY CORRECTIONS Refrigerant piping length (one way: ft.)

 

 

 

 

25 (std.)

 

40

 

 

 

65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MUZ-GE09NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MUY-GE09NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MUZ-GE12NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MUY-GE12NA

 

 

1.0

 

 

0.954

 

 

0.878

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MUZ-GE15NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MUY-GE15NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MUZ-GE18NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MUY-GE18NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3) HEATING CAPACITY (MUZ)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

Indoor air

 

 

 

 

 

 

 

 

Outdoor intake air WB temperature (˚F)

 

 

 

 

 

 

IDB (˚F)

 

5

 

15

 

 

25

 

 

35

 

 

43

45

 

 

55

 

TC

 

TPC

TC

 

TPC

TC

 

TPC

TC

 

TPC

TC

 

TPC

TC

 

TPC

TC

 

TPC

 

 

 

 

 

 

 

 

 

 

 

MUZ-GE09NA

 

75

 

4.8

 

0.45

6.3

 

0.57

7.9

 

0.67

9.4

 

0.74

10.6

 

0.78

11.0

 

0.79

12.4

 

0.82

 

70

 

5.2

 

0.43

6.7

 

0.55

8.2

 

0.65

9.6

 

0.72

10.9

 

0.76

11.2

 

0.78

12.7

 

0.81

 

 

65

 

5.5

 

0.41

6.9

 

0.52

8.6

 

0.63

10.0

 

0.70

11.2

 

0.74

11.6

 

0.75

13.0

 

0.79

MUZ-GE12NA

 

75

 

6.3

 

0.69

8.4

 

0.87

10.4

 

1.02

12.5

 

1.14

14.0

 

1.20

14.5

 

1.22

16.4

 

1.26

 

70

 

6.8

 

0.66

8.9

 

0.84

10.8

 

1.00

12.7

 

1.11

14.4

 

1.17

14.8

 

1.19

16.8

 

1.24

 

 

65

 

7.2

 

0.63

9.1

 

0.81

11.3

 

0.97

13.2

 

1.08

14.8

 

1.14

15.3

 

1.16

17.1

 

1.22

MUZ-GE15NA

 

75

 

7.9

 

0.63

10.4

 

0.79

13.1

 

0.93

1.56

 

1.03

17.6

 

1.09

18.1

 

1.10

20.5

 

1.14

 

70

 

8.6

 

0.60

11.1

 

0.76

13.5

 

0.91

15.9

 

1.01

18.0

 

1.06

18.5

 

1.08

21.0

 

1.12

 

 

65

 

9.0

 

0.57

11.3

 

0.73

14.1

 

0.87

16.5

 

0.98

18.5

 

1.03

19.1

 

1.05

21.4

 

1.10

MUZ-GE18NA

 

75

 

9.1

 

0.64

11.9

 

0.81

14.9

 

0.95

17.8

 

1.06

20.1

 

1.12

20.7

 

1.13

23.5

 

1.18

 

70

 

9.8

 

0.62

12.7

 

0.78

15.5

 

0.93

18.2

 

1.04

20.6

 

1.09

21.2

 

1.11

24.0

 

1.16

 

 

65

 

10.3

 

0.59

13.0

 

0.75

16.2

 

0.90

18.8

 

1.01

21.2

 

1.06

21.8

 

1.08

24.5

 

1.13

NOTE: 1. IDB: Intake air dry-bulb temperature TC: Total Capacity (x103 Btu/h) TPC: Total Power Consumption (kW)

2. Above data is for heating operation without any frost.

How to operate with fixed operational frequency of the compressor.

1.Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL mode or EMERGENCY HEAT mode before starting to operate the air conditioner.

2.The compressor starts with operational frequency.

3.The fan speed of the indoor unit is High.

4.This operation continues for 30 minutes.

5.In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on the remote controller.

7-2. PERFORMANCE CURVE Cooling

MUZ-GE09NA

MUY-GE09NA

SHF at rating condition = 0.76

Airflow = 307 CFM

 

13

Ind

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

capacity 3 Btu/h)

12

oor

intake

air

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

WB

temperature

 

 

 

 

 

 

 

 

(°F)

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

Total ( 10

 

 

 

 

 

 

 

 

 

71

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

67

 

7

 

 

 

 

 

 

 

 

 

63

power consumption (kW)

 

 

 

 

 

 

 

rature

(°F)

71

 

 

 

 

 

 

 

 

 

67

0.7

 

 

 

air

WB

tempe

 

 

 

intake

 

 

 

 

63

 

 

 

 

 

 

 

 

Indoor

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.5

 

 

 

 

 

 

 

 

 

 

Total

 

 

 

 

 

 

 

 

 

 

65

75

 

 

85

 

 

95

105

115

 

 

 

 

 

Outdoor intake air DB temperature (°F)

MUZ-GE12NAMUZ-GE15NA

MUY-GE12NAMUY-GE15NA

SHF at rating condition = 0.73

SHF at rating condition = 0.80

Airflow = 350 CFM

Airflow = 498 CFM

 

 

Indoor

 

 

 

 

 

 

 

 

 

18

 

 

 

 

 

 

 

 

 

 

 

15

intake

air

 

 

 

 

 

17

 

 

 

 

 

 

 

 

 

 

capacity 3 Btu/h)

14

 

WB

temperature

 

capacity 3 Btu/h)

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(°F)

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

14

Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total ( 10

11

 

 

 

 

 

 

 

 

71

Total ( 10

13

intake

air

WB te

mperat

 

 

71

10

 

 

 

 

 

 

 

 

67

12

 

 

 

ure

(°F)

67

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

63

 

11

 

 

 

 

 

 

 

63

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

power consumption (kW)

1.2

 

 

 

 

 

 

 

)

 

power consumption (kW)

1.3

 

 

 

 

 

 

 

 

 

71

1.1

 

 

 

 

 

 

rature

(°F

71

1.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

67

1.0

 

air

WB

tempe

 

67

1.1

 

 

 

 

 

 

 

 

 

63

intake

 

 

 

 

 

 

63

 

 

 

 

 

 

 

 

 

(°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rature

0.9

Indoor

 

 

 

 

 

 

 

 

1.0

 

 

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

0.9

 

 

eair

WB

tempe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.7

 

 

 

 

 

 

 

 

 

0.8

Indoor

intak

 

 

 

 

 

 

 

Total

 

 

 

 

 

 

 

 

 

Total

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

75

85

 

 

 

95

 

105

115

65

75

85

 

 

95

105

115

 

 

 

 

 

 

 

 

Outdoor intake air DB temperature (°F)

Outdoor intake air DB temperature (°F)

14

Image 14
Contents Outdoor Unit Technical Changes Part Names and Functions Specification MUZ-GE09NA MUY-GE09NA MUZ-GE12NA MUY-GE12NAMUZ-GE15NA MUY-GE15NA MUZ-GE18NA MUY-GE18NA Refrigerant charge R410A Lb ozSeer Operating RangeARI HspfOutlines and Dimensions Unit inchWiring Diagram MUZ-GE15NA MUY-GE15NA MUZ-GE18NA MUY-GE18NA Ø3/8 GE12NA Refrigerant System DiagramLEV Ø1/2 GE15NAMUZ MUZ-GE09/12/15NA MUY-GE09/12/15NA GE15Data Performance DataMUZ-GE12NAMUZ-GE15NA MUY-GE12NAMUY-GE15NA Performance Curve CoolingMUZ-GE09NA MUY-GE09NA MUZ-GE09NA MUZ-GE12NA MUZ-GE18NA MUY-GE18NAHeating MUZ MUZ-GE15NA MUZ-GE18NAMUZ-GE15NA MUY-GE15NA Condensing Pressure CoolingMUZ-GE12NA MUY-GE12NA MUZ-GE09NA MUZ-GE15NA SHF Standard Operation DataMSZ-GE09NA MSZ-GE12NA MSY-GE09NA MSY-GE12NA MSZ-GE09NA, MSY-GE09NA MSZ-GE12NA, MSY-GE12NAMUZ-GE15NA MUZ-GE18NA MSZ-GE15NA MSZ-GE18NA MSY-GE15NA MSY-GE18NAMSZ-GE15NA, MSY-GE15NA MSZ-GE18NA, MSY-GE18NA MUZ-GE15NA MUZ-GE18NA MUY-GE15NA MUY-GE18NAHOW to Operate FIXED-FREQUENCY Operation Test run operation Correction of Cooling capacityR.V. Coil Control MUZ Actuator ControlOutdoor FAN Motor Control Relation Between Main Sensor and ActuatorChange in Defrost Setting MUZ Service FunctionsTroubleshooting PRE-HEAT Control SettingFailure Mode Recall Function Operational procedure Outdoor unit failure mode table LEDTroubleshooting Check Table GE09/12 GE15 GE18 Trouble Criterion of Main PartsGE09 GE12 GE15/18 Troubleshooting Flow How to check inverter/compressorCheck of open phase Check of compressorCheck of compressor start failure Check of compressor windingCheck of compressor operation time BLK WHT BLK RED WHT REDCheck of outdoor thermistors Unit operates Cool mode even if it is set to Heat modeUnit operates Heat mode even if it is set to Cool mode Check of R.V. coil MUZMUZ-GE09/12/15NA MUY-GE09/12/15NA Check of outdoor fan motorCheck of power supply Check of LEV Expansion valve Check of inverter P.C. board Emergency OperationHow to check miswiring and serial signal error Electromagnetic noise enters into TV sets or radios LED LEV Test Point Diagram and VoltageInverter P.C. board LED Disassembly Instructions Removing the cabinet PhotoPhoto Removing the discharge temperature thermistor Removing the inverter assembly, inverter P.C. board PhotoPhoto 4 Inverter assembly Removing R.V. coil MUZRemoving outdoor fan motor Photo Removing the compressor and 4-way valveMUZ-GE18NA MUY-GE18NA Operating Procedure Photos Removing R.V. coil Photo5Removing outdoor fan motor Page Page Made in Japan New publication, effective JulDistributed in Jul . No. OBH 549

MUZ-GE09NA, MUZ-GE15NA, MUY-GE15NA, MUZ-GE18NA, MUZ-GE12NA specifications

Mitsubishi Electronics offers a range of advanced air conditioning systems, including the MUY-GE12NA, MUY-GE18NA, MUY-GE09NA, MUZ-GE12NA, and MUZ-GE18NA models. These units are designed for optimal energy efficiency and superior comfort, making them ideal for residential and commercial applications.

One of the standout features of these models is their inverter technology. By adjusting the compressor speed according to the cooling or heating demand, inverter systems provide precise temperature control while significantly reducing energy consumption compared to traditional units. This not only translates to lower utility bills but also less environmental impact.

The MUY-GE series units come with a user-friendly remote control that allows for easy adjustments of temperature settings, fan speeds, and operational modes. Smart operation modes include cooling, heating, and dehumidification, thereby catering to various climate needs. The units also include a programmable timer, enabling users to set the air conditioner to operate at specific times, enhancing convenience and efficiency.

Another impressive characteristic is the advanced air filtration system. Mitsubishi integrates a multi-stage filtration mechanism that includes a washable pre-filter, a pleated filter, and a high-performance deodorizing filter. This ensures cleaner indoor air by effectively reducing allergens, dust, and odors, contributing to a healthier living space.

The sleek and modern design of these units also allows for easy installation and compatibility with various interior settings. The MUY-GE09NA, MUY-GE12NA, and MUY-GE18NA indoor units are designed to be compact and unobtrusive, while the outdoor units (MUZ series) are engineered for durability and quiet operation.

Noise levels are another critical aspect where Mitsubishi excels. These air conditioning systems operate quietly, making them suitable for bedrooms, offices, and other noise-sensitive environments. Their Whisper-Quiet technology ensures that sound levels during operation remain low, promoting a peaceful atmosphere.

Mitsubishi Electronics ensures customer satisfaction with robust support and warranty options, emphasizing quality and reliability. In summary, the MUY-GE12NA, MUY-GE18NA, MUY-GE09NA, MUZ-GE12NA, and MUZ-GE18NA models stand out for their energy-efficient inverter technology, user-friendly controls, advanced air filtration, sleek design, and quiet operation, making them a smart choice for modern cooling and heating needs.