Mitsubishi Electronics MUY-GE12NA, MUY-GE15NA, MUY-GE18NA, MUY-GE09NA Failure Mode Recall Function

Page 24
Repeated cycle

10-2. FAILURE MODE RECALL FUNCTION

Outline of the function

This air conditioner can memorize the abnormal condition which has occurred once.

Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled.

1. Flow chart of failure mode recall function for the indoor/outdoor unit

Operational procedure

The cause of abnormality cannot be found because the abnormality does not recur.

Setting up the failure mode recall function

Turn ON the power supply. <Preparation of the remote controller>

While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button.

First, release RESET button.

And release the other two buttons after all LCD in operation display section of the remote controller is displayed after 3 seconds.

Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1

1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.

Does the upper lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds?

Blinks: Either indoor or outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the upper lamp of OPERATION INDICATOR lamp. 2

 

 

Yes

Judgment of indoor/outdoor abnormality

 

(Blinks)

 

Before blinking, does the upper lamp of OPERATION INDICA- TOR lamp stay ON for 3 seconds?

Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.

No

No (OFF)

Yes

Indoor unit is normal.

But the outdoor unit might be abnormal because there are some abnor- malities that can not be recalled with this way.

Confirm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 10-2.2)

 

The indoor unit is abnormal.

 

The outdoor unit is abnormal.

 

Check the blinking pattern, and confirm the abnormal point with the indoor unit

 

Check the blinking pattern, and confirm the abnormal point with the

 

failure mode table. (Refer to indoor unit service manual.)

 

outdoor unit failure mode table. (Refer to 10-2.3)

 

Make sure to check at least two consecutive blinking cycles. 2

 

Make sure to check at least two consecutive blinking cycles. 3

Releasing the failure mode recall function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Release the failure mode recall function by the following procedures.

 

 

 

 

 

Turn OFF the power supply and turn it ON again.

 

 

 

 

 

Press RESET button of the remote controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Repair the defective parts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Deleting the memorized abnormal condition

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above.

Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.

Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.

NOTE: 1. Make sure to release the failure mode recall function once it is set up, otherwise the unit cannot operate properly.

2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.

2. Blinking pattern when the indoor unit is abnormal:

 

 

 

 

Blinking at 0.5-

 

 

 

 

 

 

 

 

 

 

 

 

Blinking at 0.5-

 

 

 

 

 

 

 

 

 

2.5-second OFF

second interval

 

2.5-second OFF second interval

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Beeps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Beeps

 

 

 

Beeps

 

 

 

Repeated cycle

 

 

 

 

 

 

 

Repeated cycle

Repeated cycle

3.Blinking pattern when the outdoor unit is abnormal:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5-second OFF

 

 

 

3-second ON

 

 

 

Blinking at 0.5-

 

 

 

2.5-second OFF

3-second ON

 

 

 

 

 

 

 

 

 

second interval

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No beep

 

 

 

 

 

 

 

Beeps

 

 

 

 

 

 

 

 

 

 

No beep

Repeated cycle

Blinking at 0.5- second interval

Beeps

Repeated cycle

24

Image 24
Contents Outdoor Unit Technical Changes Part Names and Functions Specification MUZ-GE09NA MUY-GE09NA MUZ-GE12NA MUY-GE12NAMUZ-GE15NA MUY-GE15NA MUZ-GE18NA MUY-GE18NA Refrigerant charge R410A Lb ozOperating Range ARISeer HspfOutlines and Dimensions Unit inchWiring Diagram MUZ-GE15NA MUY-GE15NA MUZ-GE18NA MUY-GE18NA Refrigerant System Diagram LEVØ3/8 GE12NA Ø1/2 GE15NAMUZ MUZ-GE09/12/15NA MUY-GE09/12/15NA GE15Data Performance DataPerformance Curve Cooling MUZ-GE09NA MUY-GE09NAMUZ-GE12NAMUZ-GE15NA MUY-GE12NAMUY-GE15NA MUZ-GE18NA MUY-GE18NA Heating MUZMUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NACondensing Pressure Cooling MUZ-GE12NA MUY-GE12NAMUZ-GE15NA MUY-GE15NA MUZ-GE09NA MUZ-GE15NA Standard Operation Data MSZ-GE09NA MSZ-GE12NA MSY-GE09NA MSY-GE12NASHF MSZ-GE09NA, MSY-GE09NA MSZ-GE12NA, MSY-GE12NAMSZ-GE15NA MSZ-GE18NA MSY-GE15NA MSY-GE18NA MSZ-GE15NA, MSY-GE15NA MSZ-GE18NA, MSY-GE18NAMUZ-GE15NA MUZ-GE18NA MUZ-GE15NA MUZ-GE18NA MUY-GE15NA MUY-GE18NAHOW to Operate FIXED-FREQUENCY Operation Test run operation Correction of Cooling capacityActuator Control Outdoor FAN Motor ControlR.V. Coil Control MUZ Relation Between Main Sensor and ActuatorService Functions TroubleshootingChange in Defrost Setting MUZ PRE-HEAT Control SettingFailure Mode Recall Function Operational procedure Outdoor unit failure mode table LEDTroubleshooting Check Table Trouble Criterion of Main Parts GE09 GE12 GE15/18GE09/12 GE15 GE18 How to check inverter/compressor Check of open phaseTroubleshooting Flow Check of compressorCheck of compressor winding Check of compressor operation timeCheck of compressor start failure BLK WHT BLK RED WHT REDUnit operates Cool mode even if it is set to Heat mode Unit operates Heat mode even if it is set to Cool modeCheck of outdoor thermistors Check of R.V. coil MUZMUZ-GE09/12/15NA MUY-GE09/12/15NA Check of outdoor fan motorCheck of power supply Check of LEV Expansion valve Check of inverter P.C. board Emergency OperationHow to check miswiring and serial signal error Electromagnetic noise enters into TV sets or radios Test Point Diagram and Voltage Inverter P.C. boardLED LEV LED Disassembly Instructions Removing the cabinet PhotoRemoving the inverter assembly, inverter P.C. board Photo Photo 4 Inverter assemblyPhoto Removing the discharge temperature thermistor Removing R.V. coil MUZRemoving outdoor fan motor Photo Removing the compressor and 4-way valveMUZ-GE18NA MUY-GE18NA Operating Procedure Photos Removing R.V. coil Photo5Removing outdoor fan motor Page Page New publication, effective Jul Distributed in Jul . No. OBH 549Made in Japan

MUZ-GE09NA, MUZ-GE15NA, MUY-GE15NA, MUZ-GE18NA, MUZ-GE12NA specifications

Mitsubishi Electronics offers a range of advanced air conditioning systems, including the MUY-GE12NA, MUY-GE18NA, MUY-GE09NA, MUZ-GE12NA, and MUZ-GE18NA models. These units are designed for optimal energy efficiency and superior comfort, making them ideal for residential and commercial applications.

One of the standout features of these models is their inverter technology. By adjusting the compressor speed according to the cooling or heating demand, inverter systems provide precise temperature control while significantly reducing energy consumption compared to traditional units. This not only translates to lower utility bills but also less environmental impact.

The MUY-GE series units come with a user-friendly remote control that allows for easy adjustments of temperature settings, fan speeds, and operational modes. Smart operation modes include cooling, heating, and dehumidification, thereby catering to various climate needs. The units also include a programmable timer, enabling users to set the air conditioner to operate at specific times, enhancing convenience and efficiency.

Another impressive characteristic is the advanced air filtration system. Mitsubishi integrates a multi-stage filtration mechanism that includes a washable pre-filter, a pleated filter, and a high-performance deodorizing filter. This ensures cleaner indoor air by effectively reducing allergens, dust, and odors, contributing to a healthier living space.

The sleek and modern design of these units also allows for easy installation and compatibility with various interior settings. The MUY-GE09NA, MUY-GE12NA, and MUY-GE18NA indoor units are designed to be compact and unobtrusive, while the outdoor units (MUZ series) are engineered for durability and quiet operation.

Noise levels are another critical aspect where Mitsubishi excels. These air conditioning systems operate quietly, making them suitable for bedrooms, offices, and other noise-sensitive environments. Their Whisper-Quiet technology ensures that sound levels during operation remain low, promoting a peaceful atmosphere.

Mitsubishi Electronics ensures customer satisfaction with robust support and warranty options, emphasizing quality and reliability. In summary, the MUY-GE12NA, MUY-GE18NA, MUY-GE09NA, MUZ-GE12NA, and MUZ-GE18NA models stand out for their energy-efficient inverter technology, user-friendly controls, advanced air filtration, sleek design, and quiet operation, making them a smart choice for modern cooling and heating needs.