Mitsubishi Electronics MUZ-GE12NA, MUY-GE12NA How to check miswiring and serial signal error

Page 36

M How to check miswiring and serial signal error

Turn OFF the power supply.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there rated voltage in the power supply?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check the power supply.

 

 

No

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn ON the power supply.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there rated voltage between outdoor terminal block S1 and S2?

Check the wiring.

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

Press EMERGENCY OPERATION switch once.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Does the OPERATION INDICATOR lamp light

 

 

 

 

 

 

 

 

 

 

 

 

 

up? <Confirmation of the power to the indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

unit>

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

Is there any miswiring,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is serial signal error indicated 6 minutes later?

 

 

poor contact, or wire

 

 

 

 

 

 

 

disconnection of the

 

 

 

Correct them.

 

No

 

Yes

 

 

Yes

 

indoor/outdoor connect-

 

 

 

 

 

 

 

 

 

 

 

ing wire?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

Turn OFF the power supply.

 

B

Check once more if the indoor/outdoor

 

connecting wire is not miswiring.

 

 

 

Short-circuit outdoor terminal block S2

 

 

 

and S3. 1

 

 

 

 

 

 

 

 

 

 

 

 

Turn ON the power supply.

 

 

 

 

 

 

1. Miswiring may damage indoor electronic control P.C. board during the operation.

Be sure to confirm the wiring is correct before the opera- tion starts.

3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board or the outdoor electronic control P.C. board is normal, LED blinks 6 times after 3 minutes.

Is the bus-bar voltage of the inverter P.C. board or the outdoor electronic control P.C. board normal. (Refer

to "TEST POINT DIAGRAM AND VOLTAGE" in this manual.)

No

Yes

Check of power supply. (Refer to 10-5..)

Does the LED on the inverter P.C. board or the outdoor electronic control P.C.

 

 

Replace the inverter P.C. board or the outdoor

 

board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"?

3

 

 

 

 

 

 

electronic control P.C. board. 2

 

No

 

Yes

 

 

 

 

 

(Lighted

 

 

 

 

 

 

 

 

 

 

 

2. Be careful of the residual voltage of smoothing

 

 

 

 

 

 

or not

 

 

 

 

 

 

 

 

lighted)

 

capacitor.

Turn OFF the power supply.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remove the short-circuit between outdoor terminal block S2 and S3.

 

 

 

 

 

 

 

 

 

 

Turn ON the power supply.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check the wiring

 

 

 

 

 

 

 

 

 

 

Is there rated voltage between indoor terminal block S1 and S2?

 

 

 

 

 

If there are any error of the indoor/outdoor connecting wire:

 

 

 

 

 

 

such as the damage of the wire, intermediate connection,

 

 

<Confirmation of power voltage>

 

 

No

 

 

 

 

 

 

and/or poor contact to the terminal block, replace the indoor/

 

 

Yes

 

 

 

 

 

outdoor connecting wire.

 

 

 

Is there amplitude of 10 to 20 VDC between indoor terminal block S2

 

 

 

 

 

and S3? <Confirmation of serial signal>

 

No

 

 

 

 

 

Yes

 

 

 

 

 

 

A

Is there 2 VDC or less between CN10A (+)

 

 

 

• Turn OFF inverter-controlled lighting

 

 

 

and JPG (GND)(-) on the indoor electronic

 

 

 

equipment.

 

control P.C. board?

 

 

 

 

 

• Turn OFF the power supply and then

Yes

No

 

 

 

 

turn ON again.

 

 

 

 

 

 

 

 

 

 

 

 

• Press EMERGENCY OPERATION

Is there 2 VDC or less between

Is there 2 VDC or less between

 

switch.

 

 

 

CN10A

(+) and JPG (GND)(-) on

CN10A

(+) and JPG (GND)(-) on

 

 

• Reinstall

the indoor electronic control P.C.

the indoor electronic control P.C.

Yes

 

board?

 

 

board?

 

 

 

either the unit

 

No

Yes

 

No

 

 

or the light

 

 

 

 

 

 

 

away from

Replace the indoor power

Replace the indoor elec-

 

 

Is serial signal

each other.

P.C. board and the indoor

tronic control P.C. board.

 

 

error indicated 6

No • Attach a filter

terminal P.C. board

 

 

 

 

minutes later?

on remote

 

 

 

 

 

 

Yes

control receiv-

 

 

 

 

 

 

ing section

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of the indoor

 

 

 

 

 

 

B

unit.

 

 

 

 

 

 

36

Image 36
Contents Outdoor Unit Technical Changes Part Names and Functions Specification MUZ-GE09NA MUY-GE09NA MUZ-GE12NA MUY-GE12NAMUZ-GE15NA MUY-GE15NA MUZ-GE18NA MUY-GE18NA Refrigerant charge R410A Lb ozOperating Range ARISeer HspfOutlines and Dimensions Unit inchWiring Diagram MUZ-GE15NA MUY-GE15NA MUZ-GE18NA MUY-GE18NA Refrigerant System Diagram LEVØ3/8 GE12NA Ø1/2 GE15NAMUZ MUZ-GE09/12/15NA MUY-GE09/12/15NA GE15Data Performance DataPerformance Curve Cooling MUZ-GE09NA MUY-GE09NAMUZ-GE12NAMUZ-GE15NA MUY-GE12NAMUY-GE15NA MUZ-GE18NA MUY-GE18NA Heating MUZMUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NACondensing Pressure Cooling MUZ-GE12NA MUY-GE12NAMUZ-GE15NA MUY-GE15NA MUZ-GE09NA MUZ-GE15NA Standard Operation Data MSZ-GE09NA MSZ-GE12NA MSY-GE09NA MSY-GE12NASHF MSZ-GE09NA, MSY-GE09NA MSZ-GE12NA, MSY-GE12NAMSZ-GE15NA MSZ-GE18NA MSY-GE15NA MSY-GE18NA MSZ-GE15NA, MSY-GE15NA MSZ-GE18NA, MSY-GE18NAMUZ-GE15NA MUZ-GE18NA MUZ-GE15NA MUZ-GE18NA MUY-GE15NA MUY-GE18NAHOW to Operate FIXED-FREQUENCY Operation Test run operation Correction of Cooling capacityActuator Control Outdoor FAN Motor ControlR.V. Coil Control MUZ Relation Between Main Sensor and ActuatorService Functions TroubleshootingChange in Defrost Setting MUZ PRE-HEAT Control SettingFailure Mode Recall Function Operational procedure Outdoor unit failure mode table LEDTroubleshooting Check Table Trouble Criterion of Main Parts GE09 GE12 GE15/18GE09/12 GE15 GE18 How to check inverter/compressor Check of open phaseTroubleshooting Flow Check of compressorCheck of compressor winding Check of compressor operation timeCheck of compressor start failure BLK WHT BLK RED WHT REDUnit operates Cool mode even if it is set to Heat mode Unit operates Heat mode even if it is set to Cool modeCheck of outdoor thermistors Check of R.V. coil MUZMUZ-GE09/12/15NA MUY-GE09/12/15NA Check of outdoor fan motorCheck of power supply Check of LEV Expansion valve Check of inverter P.C. board Emergency OperationHow to check miswiring and serial signal error Electromagnetic noise enters into TV sets or radios Test Point Diagram and Voltage Inverter P.C. boardLED LEV LED Disassembly Instructions Removing the cabinet PhotoRemoving the inverter assembly, inverter P.C. board Photo Photo 4 Inverter assemblyPhoto Removing the discharge temperature thermistor Removing R.V. coil MUZRemoving outdoor fan motor Photo Removing the compressor and 4-way valveMUZ-GE18NA MUY-GE18NA Operating Procedure Photos Removing R.V. coil Photo5Removing outdoor fan motor Page Page New publication, effective Jul Distributed in Jul . No. OBH 549Made in Japan

MUZ-GE09NA, MUZ-GE15NA, MUY-GE15NA, MUZ-GE18NA, MUZ-GE12NA specifications

Mitsubishi Electronics offers a range of advanced air conditioning systems, including the MUY-GE12NA, MUY-GE18NA, MUY-GE09NA, MUZ-GE12NA, and MUZ-GE18NA models. These units are designed for optimal energy efficiency and superior comfort, making them ideal for residential and commercial applications.

One of the standout features of these models is their inverter technology. By adjusting the compressor speed according to the cooling or heating demand, inverter systems provide precise temperature control while significantly reducing energy consumption compared to traditional units. This not only translates to lower utility bills but also less environmental impact.

The MUY-GE series units come with a user-friendly remote control that allows for easy adjustments of temperature settings, fan speeds, and operational modes. Smart operation modes include cooling, heating, and dehumidification, thereby catering to various climate needs. The units also include a programmable timer, enabling users to set the air conditioner to operate at specific times, enhancing convenience and efficiency.

Another impressive characteristic is the advanced air filtration system. Mitsubishi integrates a multi-stage filtration mechanism that includes a washable pre-filter, a pleated filter, and a high-performance deodorizing filter. This ensures cleaner indoor air by effectively reducing allergens, dust, and odors, contributing to a healthier living space.

The sleek and modern design of these units also allows for easy installation and compatibility with various interior settings. The MUY-GE09NA, MUY-GE12NA, and MUY-GE18NA indoor units are designed to be compact and unobtrusive, while the outdoor units (MUZ series) are engineered for durability and quiet operation.

Noise levels are another critical aspect where Mitsubishi excels. These air conditioning systems operate quietly, making them suitable for bedrooms, offices, and other noise-sensitive environments. Their Whisper-Quiet technology ensures that sound levels during operation remain low, promoting a peaceful atmosphere.

Mitsubishi Electronics ensures customer satisfaction with robust support and warranty options, emphasizing quality and reliability. In summary, the MUY-GE12NA, MUY-GE18NA, MUY-GE09NA, MUZ-GE12NA, and MUZ-GE18NA models stand out for their energy-efficient inverter technology, user-friendly controls, advanced air filtration, sleek design, and quiet operation, making them a smart choice for modern cooling and heating needs.