Mitsubishi Electronics MUY-GE09NA, MUY-GE12NA, MUY-GE15NA, MUY-GE18NA Troubleshooting Check Table

Page 27

10-3. TROUBLESHOOTING CHECK TABLE

No.

Symptom

LED indication

Abnormal point/

Condition

 

Remedy

Condition

 

 

 

 

 

 

 

 

Outdoor

1-time flash every

Outdoor power sys-

Overcurrent protection stop is continuously performed 3 times

•Reconnect connector of compressor.

1

unit does

2.5 seconds

tem

within 1 minute after the compressor gets started, or failure of re-

•Refer to 10-5. "How to check inverter/

not oper-

 

 

start of compressor has repeated 24 times.

compressor".

 

 

ate.

 

 

 

•Check stop valve.

 

 

 

Outdoor thermistors

Discharge temperature thermistor, fin temperature thermistor, de-

•Refer to 10-5. "Check of outdoor

2

 

 

 

frost thermistor, outdoor heat exchanger temperature thermistor,

thermistors".

 

 

 

 

P.C. board temperature thermistor or ambient temperature therm-

 

 

 

 

 

 

 

 

 

 

 

 

istor shorts or opens during compressor running.

 

 

3

 

 

Outdoor control sys-

Nonvolatile memory data cannot be read properly.

•Replace inverter P.C. board.

 

 

tem

(POWER lamp of the indoor unit lights up or flashes 7 times.)

 

 

 

 

 

 

 

 

4

 

6-time flash

Serial signal

The communication fails between the indoor and outdoor unit for

•Refer to 10-5.

"How to check miswir-

 

2.5 seconds OFF

 

3 minutes.

ing and serial signal error.

 

 

 

5

 

11-time flash

Stop valve/

Closed valve is detected by compressor current.

•Check stop valve.

 

2.5 seconds OFF

Closed valve

 

 

 

 

 

 

 

 

6

 

14-time flash

Outdoor unit

Outdoor unit is defective.

•Refer to 10-2.2. "Flow chart of the de-

 

2.5 seconds OFF

(Other abnormality)

 

tailed outdoor unit failure mode recall

 

 

 

 

 

function".

 

 

'Outdoor

2-time flash

Overcurrent protec-

Large current flows into intelligent power module.

•Reconnect connector of compressor.

7

unit stops

2.5 seconds OFF

tion

When overcurrent protection occurs within 10 seconds after

•Refer to 10-5. "How to check inverter/

and re-

 

 

compressor starts, compressor restarts after 15 seconds.

compressor".

 

 

starts 3

 

 

 

•Check stop valve.

 

minutes

 

 

 

 

 

 

3-time flash

Discharge tempera-

Temperature of discharge temperature thermistor exceeds 241°F

•Check refrigerant circuit and refrigerant

 

later' is

8

2.5 seconds OFF

ture overheat protec-

(116°C), compressor stops. Compressor can restart if discharge

amount.

 

repeated.

"Check of LEV".

 

tion

temperature thermistor reads 212°F (100°C) or less 3 minutes

•Refer to 10-5.

 

 

 

 

later.

 

 

 

 

4-time flash

Fin temperature /P.C.

Temperature of fin temperature thermistor on the heat sink ex-

•Check around outdoor unit.

9

 

2.5 seconds OFF

board temperature

ceeds 167 ~ 176°F (75 ~ 80°C) or temperature of P.C. board tem-

•Check outdoor unit air passage.

 

 

thermistor overheat

perature thermistor on the inverter P.C. board exceeds 158 ~ 167

•Refer to 10-5. "Check of outdoor fan

 

 

 

 

 

 

protection

°F (70 ~ 75°C).

motor".

 

10

 

5-time flash

High pressure pro-

Temperature of indoor coil thermistor exceeds 158°F (70°C) in

•Check refrigerant circuit and refrigerant

 

2.5 seconds OFF

tection

HEAT mode. Temperature of outdoor heat exchanger temperature

amount.

 

 

 

 

(MUZ)

thermistor exceeds 158°F (70°C) in COOL mode.

•Check stop valve.

11

 

8-time flash

Compressor syn-

The waveform of compressor current is distorted.

•Reconnect connector of compressor.

 

2.5 seconds OFF

chronous abnormal-

 

•Refer to 10-5. "How to check inverter/

 

 

 

ity

 

compressor".

 

 

 

10-time flash

Outdoor fan motor

Outdoor fan has stopped 3 times in a row within 30 seconds after

•Refer to 10-5. "Check of outdoor fan

12

 

2.5 seconds OFF

 

outdoor fan start-up.

motor.

 

 

 

 

 

•Refer to 10-5. "Check of inverter P.C.

 

 

 

 

 

board.

 

13

 

12-time flash

Each phase current

Each phase current of compressor cannot be detected normally.

•Refer to 10-5.

"How to check inverter/

 

2.5 seconds OFF

of compressor

 

compressor".

 

 

 

 

 

14

 

13-time flash

DC voltage

DC voltage of inverter cannot be detected normally.

•Refer to 10-5.

"How to check inverter/

 

2.5 seconds OFF

 

 

compressor".

 

 

 

 

 

 

15

Outdoor

1-time flash

Frequency drop by

Current from power outlet is nearing Max. fuse size.

The unit is normal, but check the follow-

unit oper-

2.5 seconds OFF

current protection

 

ing.

 

 

ates.

 

 

 

•Check if indoor filters are clogged.

 

3-time flash

Frequency drop by

Temperature of indoor coil thermistor exceeds 131°F (55°C) in

 

 

•Check if refrigerant is short.

 

 

2.5 seconds OFF

high pressure protec-

HEAT mode, compressor frequency lowers.

 

 

•Check if indoor/outdoor unit air circula-

 

 

 

tion

 

16

 

 

 

tion is short cycled.

 

 

Frequency drop by

Indoor coil thermistor reads 46°F (8°C) or less in COOL mode,

 

 

 

 

 

 

 

 

defrosting in COOL

compressor frequency lowers.

 

 

 

 

 

mode

 

 

 

 

 

4-time flash

Frequency drop by

Temperature of discharge temperature thermistor exceeds 232°F

•Check refrigerant circuit and refrigerant

17

 

2.5 seconds OFF

discharge tempera-

(111°C), compressor frequency lowers.

amount.

"Check of LEV".

 

 

ture protection

 

•Refer to 10-5.

 

 

 

 

 

•Refer to 10-5. "Check of outdoor

 

 

 

 

 

thermistors".

 

18

Outdoor

7-time flash

Low discharge tem-

Temperature of discharge temperature thermistor has been 122°F

•Refer to 10-5.

"Check of LEV".

unit oper-

2.5 seconds OFF

perature protection

(50°C) or less for 20 minutes.

•Check refrigerant circuit and refrigerant

 

ates.

 

 

 

amount.

 

 

 

8-time flash

PAM protection PAM:

The overcurrent flows into IGBT (Insulated Gate Bipolar transis-

This is not malfunction. PAM protection

19

 

2.5 seconds OFF

Pulse Amplitude

tor: TR821) or the bus-bar voltage reaches 320 V or more, PAM

will be activated in the following cases:

 

 

Modulation

stops and restarts.

1 Instantaneous power voltage drop

 

 

 

 

 

(Short time power failure)

 

 

 

 

 

2 When the power supply voltage is high.

 

 

9-time flash

Inverter check mode

The connector of compressor is disconnected, inverter check

•Check if the connector of the compres-

20

 

2.5 seconds OFF

 

mode starts.

sor is correctly connected. Refer to

 

 

 

 

10-5. "How to check inverter/compres-

 

 

 

 

 

 

 

 

 

 

sor".

 

NOTE: 1. The location of LED is illustrated at the right figure. Refer to 10-6.1. 2. LED is lighted during normal operation.

The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF. Flashing (Example) When the flashing frequency is “2”.

ON

OFF

2.5-second OFF

0.5-second ON

2.5-second OFF

0.5-second ON

Inverter P.C. board (Parts side)

LED

Flashing →

27

Image 27
Contents Outdoor Unit Technical Changes Part Names and Functions MUZ-GE09NA MUY-GE09NA MUZ-GE12NA MUY-GE12NA SpecificationRefrigerant charge R410A Lb oz MUZ-GE15NA MUY-GE15NA MUZ-GE18NA MUY-GE18NAHspf Operating RangeARI SeerUnit inch Outlines and DimensionsWiring Diagram MUZ-GE15NA MUY-GE15NA MUZ-GE18NA MUY-GE18NA Ø1/2 GE15NA Refrigerant System DiagramLEV Ø3/8 GE12NAMUZ-GE09/12/15NA MUY-GE09/12/15NA GE15 MUZPerformance Data DataPerformance Curve Cooling MUZ-GE09NA MUY-GE09NAMUZ-GE12NAMUZ-GE15NA MUY-GE12NAMUY-GE15NA MUZ-GE15NA MUZ-GE18NA MUZ-GE18NA MUY-GE18NAHeating MUZ MUZ-GE09NA MUZ-GE12NACondensing Pressure Cooling MUZ-GE12NA MUY-GE12NAMUZ-GE15NA MUY-GE15NA MUZ-GE09NA MUZ-GE15NA MSZ-GE09NA, MSY-GE09NA MSZ-GE12NA, MSY-GE12NA Standard Operation DataMSZ-GE09NA MSZ-GE12NA MSY-GE09NA MSY-GE12NA SHFMUZ-GE15NA MUZ-GE18NA MUY-GE15NA MUY-GE18NA MSZ-GE15NA MSZ-GE18NA MSY-GE15NA MSY-GE18NAMSZ-GE15NA, MSY-GE15NA MSZ-GE18NA, MSY-GE18NA MUZ-GE15NA MUZ-GE18NACorrection of Cooling capacity HOW to Operate FIXED-FREQUENCY Operation Test run operationRelation Between Main Sensor and Actuator Actuator ControlOutdoor FAN Motor Control R.V. Coil Control MUZPRE-HEAT Control Setting Service FunctionsTroubleshooting Change in Defrost Setting MUZFailure Mode Recall Function Operational procedure LED Outdoor unit failure mode tableTroubleshooting Check Table Trouble Criterion of Main Parts GE09 GE12 GE15/18GE09/12 GE15 GE18 Check of compressor How to check inverter/compressorCheck of open phase Troubleshooting FlowBLK WHT BLK RED WHT RED Check of compressor windingCheck of compressor operation time Check of compressor start failureCheck of R.V. coil MUZ Unit operates Cool mode even if it is set to Heat modeUnit operates Heat mode even if it is set to Cool mode Check of outdoor thermistorsCheck of outdoor fan motor MUZ-GE09/12/15NA MUY-GE09/12/15NACheck of power supply Check of LEV Expansion valve Emergency Operation Check of inverter P.C. boardHow to check miswiring and serial signal error Electromagnetic noise enters into TV sets or radios Test Point Diagram and Voltage Inverter P.C. boardLED LEV LED Removing the cabinet Photo Disassembly InstructionsRemoving R.V. coil MUZ Removing the inverter assembly, inverter P.C. board PhotoPhoto 4 Inverter assembly Photo Removing the discharge temperature thermistorRemoving the compressor and 4-way valve Removing outdoor fan motor PhotoMUZ-GE18NA MUY-GE18NA Operating Procedure Photos Photo5 Removing R.V. coilRemoving outdoor fan motor Page Page New publication, effective Jul Distributed in Jul . No. OBH 549Made in Japan

MUZ-GE09NA, MUZ-GE15NA, MUY-GE15NA, MUZ-GE18NA, MUZ-GE12NA specifications

Mitsubishi Electronics offers a range of advanced air conditioning systems, including the MUY-GE12NA, MUY-GE18NA, MUY-GE09NA, MUZ-GE12NA, and MUZ-GE18NA models. These units are designed for optimal energy efficiency and superior comfort, making them ideal for residential and commercial applications.

One of the standout features of these models is their inverter technology. By adjusting the compressor speed according to the cooling or heating demand, inverter systems provide precise temperature control while significantly reducing energy consumption compared to traditional units. This not only translates to lower utility bills but also less environmental impact.

The MUY-GE series units come with a user-friendly remote control that allows for easy adjustments of temperature settings, fan speeds, and operational modes. Smart operation modes include cooling, heating, and dehumidification, thereby catering to various climate needs. The units also include a programmable timer, enabling users to set the air conditioner to operate at specific times, enhancing convenience and efficiency.

Another impressive characteristic is the advanced air filtration system. Mitsubishi integrates a multi-stage filtration mechanism that includes a washable pre-filter, a pleated filter, and a high-performance deodorizing filter. This ensures cleaner indoor air by effectively reducing allergens, dust, and odors, contributing to a healthier living space.

The sleek and modern design of these units also allows for easy installation and compatibility with various interior settings. The MUY-GE09NA, MUY-GE12NA, and MUY-GE18NA indoor units are designed to be compact and unobtrusive, while the outdoor units (MUZ series) are engineered for durability and quiet operation.

Noise levels are another critical aspect where Mitsubishi excels. These air conditioning systems operate quietly, making them suitable for bedrooms, offices, and other noise-sensitive environments. Their Whisper-Quiet technology ensures that sound levels during operation remain low, promoting a peaceful atmosphere.

Mitsubishi Electronics ensures customer satisfaction with robust support and warranty options, emphasizing quality and reliability. In summary, the MUY-GE12NA, MUY-GE18NA, MUY-GE09NA, MUZ-GE12NA, and MUZ-GE18NA models stand out for their energy-efficient inverter technology, user-friendly controls, advanced air filtration, sleek design, and quiet operation, making them a smart choice for modern cooling and heating needs.