| No. | Symptom | LED indication | Abnormal point/ | Condition | | Remedy |
| Condition | |
| | | | | | |
| | Outdoor | 1-time flash every | Outdoor power sys- | Overcurrent protection stop is continuously performed 3 times | •Reconnect connector of compressor. |
| 1 | unit does | 2.5 seconds | tem | within 1 minute after the compressor gets started, or failure of re- | •Refer to 10-5. "How to check inverter/ |
| not oper- | | | start of compressor has repeated 24 times. | compressor". | |
| | ate. | | | | •Check stop valve. |
| | | | Outdoor thermistors | Discharge temperature thermistor, fin temperature thermistor, de- | •Refer to 10-5. "Check of outdoor |
| 2 | | | | frost thermistor, outdoor heat exchanger temperature thermistor, | thermistors". | |
| | | | P.C. board temperature thermistor or ambient temperature therm- | | |
| | | | | | |
| | | | | istor shorts or opens during compressor running. | | |
| 3 | | | Outdoor control sys- | Nonvolatile memory data cannot be read properly. | •Replace inverter P.C. board. |
| | | tem | (POWER lamp of the indoor unit lights up or flashes 7 times.) | | |
| | | | | | |
| 4 | | 6-time flash | Serial signal | The communication fails between the indoor and outdoor unit for | •Refer to 10-5. | "How to check miswir- |
| | 2.5 seconds OFF | | 3 minutes. | ing and serial signal error. |
| | | |
| 5 | | 11-time flash | Stop valve/ | Closed valve is detected by compressor current. | •Check stop valve. |
| | 2.5 seconds OFF | Closed valve | | | |
| | | | | |
| 6 | | 14-time flash | Outdoor unit | Outdoor unit is defective. | •Refer to 10-2.2. "Flow chart of the de- |
| | 2.5 seconds OFF | (Other abnormality) | | tailed outdoor unit failure mode recall |
| | | | | | function". | |
| | 'Outdoor | 2-time flash | Overcurrent protec- | Large current flows into intelligent power module. | •Reconnect connector of compressor. |
| 7 | unit stops | 2.5 seconds OFF | tion | When overcurrent protection occurs within 10 seconds after | •Refer to 10-5. "How to check inverter/ |
| and re- | | | compressor starts, compressor restarts after 15 seconds. | compressor". | |
| | starts 3 | | | | •Check stop valve. |
| | minutes | | | | | |
| | 3-time flash | Discharge tempera- | Temperature of discharge temperature thermistor exceeds 241°F | •Check refrigerant circuit and refrigerant |
| | later' is |
| 8 | 2.5 seconds OFF | ture overheat protec- | (116°C), compressor stops. Compressor can restart if discharge | amount. | |
| repeated. | "Check of LEV". |
| | tion | temperature thermistor reads 212°F (100°C) or less 3 minutes | •Refer to 10-5. |
| | | | | later. | | |
| | | 4-time flash | Fin temperature /P.C. | Temperature of fin temperature thermistor on the heat sink ex- | •Check around outdoor unit. |
| 9 | | 2.5 seconds OFF | board temperature | ceeds 167 ~ 176°F (75 ~ 80°C) or temperature of P.C. board tem- | •Check outdoor unit air passage. |
| | | thermistor overheat | perature thermistor on the inverter P.C. board exceeds 158 ~ 167 | •Refer to 10-5. "Check of outdoor fan |
| | | |
| | | | protection | °F (70 ~ 75°C). | motor". | |
| 10 | | 5-time flash | High pressure pro- | Temperature of indoor coil thermistor exceeds 158°F (70°C) in | •Check refrigerant circuit and refrigerant |
| | 2.5 seconds OFF | tection | HEAT mode. Temperature of outdoor heat exchanger temperature | amount. | |
| | | | (MUZ) | thermistor exceeds 158°F (70°C) in COOL mode. | •Check stop valve. |
| 11 | | 8-time flash | Compressor syn- | The waveform of compressor current is distorted. | •Reconnect connector of compressor. |
| | 2.5 seconds OFF | chronous abnormal- | | •Refer to 10-5. "How to check inverter/ |
| | | | ity | | compressor". | |
| | | 10-time flash | Outdoor fan motor | Outdoor fan has stopped 3 times in a row within 30 seconds after | •Refer to 10-5. "Check of outdoor fan |
| 12 | | 2.5 seconds OFF | | outdoor fan start-up. | motor. | |
| | | | | •Refer to 10-5. "Check of inverter P.C. |
| | | | | | board. | |
| 13 | | 12-time flash | Each phase current | Each phase current of compressor cannot be detected normally. | •Refer to 10-5. | "How to check inverter/ |
| | 2.5 seconds OFF | of compressor | | compressor". | |
| | | | |
| 14 | | 13-time flash | DC voltage | DC voltage of inverter cannot be detected normally. | •Refer to 10-5. | "How to check inverter/ |
| | 2.5 seconds OFF | | | compressor". | |
| | | | | |
| 15 | Outdoor | 1-time flash | Frequency drop by | Current from power outlet is nearing Max. fuse size. | The unit is normal, but check the follow- |
| unit oper- | 2.5 seconds OFF | current protection | | ing. | |
| | ates. | | | | •Check if indoor filters are clogged. |
| | 3-time flash | Frequency drop by | Temperature of indoor coil thermistor exceeds 131°F (55°C) in |
| | | •Check if refrigerant is short. |
| | | 2.5 seconds OFF | high pressure protec- | HEAT mode, compressor frequency lowers. |
| | | •Check if indoor/outdoor unit air circula- |
| | | | tion | |
| 16 | | | | tion is short cycled. |
| | | Frequency drop by | Indoor coil thermistor reads 46°F (8°C) or less in COOL mode, |
| | | | | |
| | | | defrosting in COOL | compressor frequency lowers. | | |
| | | | mode | | | |
| | | 4-time flash | Frequency drop by | Temperature of discharge temperature thermistor exceeds 232°F | •Check refrigerant circuit and refrigerant |
| 17 | | 2.5 seconds OFF | discharge tempera- | (111°C), compressor frequency lowers. | amount. | "Check of LEV". |
| | | ture protection | | •Refer to 10-5. |
| | | | | | •Refer to 10-5. "Check of outdoor |
| | | | | | thermistors". | |
| 18 | Outdoor | 7-time flash | Low discharge tem- | Temperature of discharge temperature thermistor has been 122°F | •Refer to 10-5. | "Check of LEV". |
| unit oper- | 2.5 seconds OFF | perature protection | (50°C) or less for 20 minutes. | •Check refrigerant circuit and refrigerant |
| | ates. | | | | amount. | |
| | | 8-time flash | PAM protection PAM: | The overcurrent flows into IGBT (Insulated Gate Bipolar transis- | This is not malfunction. PAM protection |
| 19 | | 2.5 seconds OFF | Pulse Amplitude | tor: TR821) or the bus-bar voltage reaches 320 V or more, PAM | will be activated in the following cases: |
| | | Modulation | stops and restarts. | 1 Instantaneous power voltage drop |
| | | | | | (Short time power failure) |
| | | | | | 2 When the power supply voltage is high. |
| | | 9-time flash | Inverter check mode | The connector of compressor is disconnected, inverter check | •Check if the connector of the compres- |
| 20 | | 2.5 seconds OFF | | mode starts. | sor is correctly connected. Refer to |
| | | | | 10-5. "How to check inverter/compres- |
| | | | | |
| | | | | | sor". | |