Maintenance

Communications Errors

LEDs

If the CHS 110 module detects a communications error, the LEDs display the

 

following pattern:

 

LED display for a communications error.

 

140

 

 

CHS 110 00

 

HOT STANDBY

 

Active

 

Ready

Fault

 

Run

Bal Low

 

Pwr ok

 

 

Modbus Com Err

 

Modbus! Error A

 

Com Act Error B

 

Primary

 

 

Mem Prt Standby

 

 

Troubleshooting

1. Be sure the fiber optic cables are connected properly and functioning correctly

 

2. If the fiber optic cables are in good condition, replace the faulty CHS 110 module.

Interface Errors

 

If the Hot Standby module detects certain errors in its interface with the controller,

 

the LED display goes out momentarily as the module tries to recover. It either

 

returns to a ready state or reports the error with a blinking Com Act indicator. The

 

Com Act error patterns are described in Com Act Error Patterns, p. 209.

 

 

 

Troubleshooting 1. If you used the CHS function block, disable it and restart the system. If the Ready indicator comes on, the problem is in the CHS 110 module. If you used a configuration extension screen, go offline and change the configuration to a standalone system. Reload the program. Restart the system. If the Ready indicator comes on, the problem is in the CHS 110 module.

2.If you have replaced the Hot Standby module and the problem still occurs, replace the other components, one at a time.

3.If the problem still occurs, replace the backplane.

840 USE 106 00 January 2003