Theory of 984 HSBY Operation

The diagram below shows examples of the data transfer area for different configurations of 3x and 4x registers.

Example 1

If you have 3200 3x and 9600 4x registers, then the full allotment of 1000 3x registers will be transferred. The acutual number of 4x registers transferred will be 9008; that is, the full allotment of 9000 registers plus 8 more to reach the next highest multiple of 16.

Transfer Area

Example 2

If you have 3200 3x and 7000 4x registers, then all the 4x registers will be transferred. The full allotment of 1000 3x registers will be transferred, plus an additional 2000 3x registers to bring the total number of registers transferred to 10,000. So a total of 3000 3x registers will be transferred.

Example 3

If you have 700 3x and 9600 4x registers, then all the 3x registers will be transferred. The full allotment of 9000 4x registers will be transferred, plus an additional 300 registers to bring the total to 10,000, plus an additional 12 registers to reach the next highest multiple of 16. In all, 9312 4x registers will be transferred.