Schneider Electric 840 USE 106 0 manual Scan Transfers, Data Type

Models: 840 USE 106 0

1 226
Download 226 pages 11.66 Kb
Page 102
Image 102

Using a Quantum 984 HSBY System

Scan Transfers

Data Type

A minimum of 512 equivalent words of each data type specified in the Additional

 

State RAM area are sent in a scan, unless there are less than 512 words of that data

 

type left to be transferred. For example, if you specify 528 additional registers to be

 

transferred over three scans, the system will send the data faster than expected.

 

The first 512 additional registers are transferred in the first scan, and the remaining

 

16 registers are transferred in the second scan. On the third scan, the process

 

begins again, sending the first 512 additional registers.

 

 