Using a Quantum IEC Hot Standby System

Loading the Software

Loading and Starting with Concept 2.5, the CHS loadable is a part of the Concept install.

Concept 2.5 If you are using Concept 2.5 and for some reason the loadable is deleted, it can be reinstalled using the following procedure.

Load Software To configure a Quantum Hot Standby system, load the CHS software into the

into Controllers controllers. The software is included on a diskette in the Hot Standby Kit. Once you have installed the software, you can activate the IEC Hot Standby configuration extension.

Installing the The following steps are only necessary if the CHS loadable is not already part of

CHS loadable your Concept installation. The CHS loadable is provided on a 3 1/2" diskette

into the Concept (140 SHS 945 00) as part of your 140 CHS 210 00 Hot Standby kit. The file is named

Environment QCHSVxxx.DAT, where xxx is the three-digit version number of the software.

Step

Action

1Insert the diskette in the disk drive.

2Either create a new Concept project or open an existing one and have a PLC selected

3With the menu command Project Configurator, open the configurator.

4With Configure Loadables, open the dialog box Loadables.

5Press the command button Unpack to open the standard Windows dialog box, Unpack Loadable File. Select the loadable file, click the button OK and it is inserted into the list box Available.