Using a Quantum 984 HSBY System

Reverse Transfer Logic Example

A Reverse

The following example shows I/O ladder logic for a Primary controller that monitors

Transfer Logic

two fault lamps and the reverse transfer logic that sends status data from the

Example

Standby controller to the Primary. One fault lamp turns ON if the Standby memory

 

protect is OFF; the other lamp turns ON if the memory backup battery fails in the

 

Standby.

 

Network 1 of Segment 1

 

 

 

 

 

 

 

 

 

 

400005

 

 

 

 

 

 

 

 

 

 

400100

 

 

 

 

 

CHS

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

Network 2 of Segment 1

 

 

 

 

 

 

 

 

BLKM transfers the status of the

 

400103

 

 

 

 

 

Hot Standby status register

 

 

 

 

 

 

 

000801

 

 

(40103) to internal coils (00801)

 

BLKM

 

 

 

 

 

 

#001

 

 

 

 

 

 

 

 

 

 

 

 

 

STAT sends one register Word from

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400101

 

 

 

 

 

 

 

the standby to a reverse transfer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STAT

register (400101 in the primary.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

000815

000816

#001

 

 

(Bit 15)

(Bit 16)

 

 

 

 

(Enables STAT if this PLC is the Standby