Theory of IEC HSBY Operation

Transfer diagram The following shows a transfer diagram:

1 Scan

Primary Rack

 

IEC Logic Solve Comm Diag

IEC Logic Solve

Comm Diag

IEC Logic Solve Diag

 

CPU

 

 

 

 

 

 

 

 

 

 

State RAM & IEC

 

 

 

 

 

 

 

 

Heap download

 

 

 

 

 

 

 

 

128K

 

128K

 

128K

 

 

 

 

 

 

bytes

 

bytes

 

bytes

 

CHS

 

 

 

 

 

 

 

 

 

 

 

State RAM & IEC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heap download (Over the

 

 

 

 

 

Standby Rack

Fiber Optic HSBY link)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

128K

 

 

128K

 

 

128K

 

 

bytes

 

 

bytes

 

 

bytes

 

CHS

 

State RAM & IEC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heap download

 

 

 

 

 

 

Diag

 

Comm

Diag

 

Comm

Diag

 

CPU

 

 

 

 

 

 

 

 

 

1 Scan

Note: The size of 128K bytes state RAM memory in the timing diagram being transferred with each scan is not a fixed value. It expresses the maximum amount of data handled by the CHS module during a data transfer. This is a hardware limitation. Therefore, the maximum State RAM limitation for the IEC user is 128 K bytes. Unlike a 984 HSBY system, the Standby controller doesn’t solve any logic. With the new execs delivered with Concept 2.5, the Standby Controller solves logic in Section 1.