Ethernet Hot Standby Solution

Address Swap Times

Description

The following table details what the "time for an Address swap" comprises, such as

 

the time to close connections, time to swap IP addresses, or time to establish

 

connections.

The following table shows the swap time for each of the Ethernet services.

Service

Typical Swap Time

Maximum Swap Time

 

 

 

Swap IP Addresses

6 ms

500 ms

 

 

 

I/O Scanning

1 initial cycle of I/O Scanning

500 ms + 1 initial cycle of I/O

 

 

scanning

 

 

 

Global Data

For times, please see the

500 ms + 1 CPU scan

 

840USE11600, Quantum

 

 

NOE 771 xx Ethernet

 

 

Modules User Guide

 

 

 

 

Client Messaging

1 CPU scan

500 ms + 1 CPU scan

 

 

 

Server Messaging

1 CPU scan + the time of the

500 ms + the time of the client

 

client reestablishment

reestablishment connection

 

connection

 

 

 

 

FTP/TFTP Server

The time of the client

500 ms + the time of the client

 

reestablishment connection

reestablishment connection

 

 

 

SNMP

1 CPU scan

500 ms + 1 CPU scan

 

 

 

HTTP Server

The time of the client

500 ms + the time of the client

 

reestablishment connection

reestablishment connection

 

 

 

 

 

 

840 USE 106 00 January 2003

173

Page 173
Image 173
Schneider Electric 840 USE 106 0 manual Address Swap Times, Connections, Service Typical Swap Time Maximum Swap Time