Maintenance

Forcing a

You can force a switchover using the RDE or, if you have programmed a CHS

 

Switchover

instruction in ladder logic, a Zoom screen. The instructions are the same; however,

 

Through

in the RDE you are working with the command and status registers, while in the

 

Software

Zoom screen you are working with the command and status pages.

 

 

 

 

 

 

Step

Action

 

 

 

 

 

 

1

Addressing the Primary controller: Check the status register or page to be sure

 

 

 

one unit is designated A and the other is B. Be sure that both the Primary and

 

 

 

the Standby controllers are in run mode and that the function keyswitch override

 

 

 

has been enabled.

 

 

 

 

 

 

2

In the command register or on the command page, take the Primary controller

 

 

 

offline.

 

 

 

 

 

 

3

If you are operating on a Modbus Plus network, the programming panel is

 

 

 

automatically communicating with the Primary controller. If you are operating via

 

 

 

the Modbus or Modbus Port directly connected to the original primary controller,

 

 

 

you must reconnect the programming cable to the new Primary controller and

 

 

 

then log in again, due to the port address swap.

 

 

 

Result: The status should now show that the original Primary controller is offline

 

 

 

and that the Standby is now functioning as the Primary unit. Refer to Command

 

 

 

Register, p. 76.

 

 

 

 

 

 

4

Check the LED displays on the Hot Standby modules to confirm that the

 

 

 

switchover has taken place. The Primary indicator on the original Primary unit

 

 

 

should be extinguished, while the Primary indicator on the original Standby unit

 

 

 

should be a steady green.

 

 

 

 

 

 

5

In the command register or on the command page, return the original Primary

 

 

 

unit to RUN mode. The status register or page and the LED display on the front

 

 

 

panel of the Hot Standby module should now show that unit in Standby mode.

 

 

 

 

 

 

 

 

 

204

840 USE 106 00 January 2003