Overview of Quantum Hot Standby

Function

Beneath the LED display on the face of each CHS 110 control panel is a function

Keyswitch

keyswitch. It has three positions: Off Line, Xfer (transfer) and Run. You may use this

 

switch to force transfer of control functions or to copy the full program from the

 

Primary controller to the Standby.

 

The following illustration shows a function keyswitch with three positions: Off LIne,

 

Xfer and Run.

 

 

Off

 

 

Line

Xfer

Run

 

Note: For security or convenience, you can disable the function keyswitch with a

 

software override. Once the keyswitch is disabled, you can set the module to run

 

or offline mode with software. This can be especially helpful when the module is

 

not easily accessible.

Designation

 

 

A slide switch located below and to the right of the keyswitch is used to designate

Slide Switch and

the controller as A or B. One unit must be designated as A and the other as B.

Update Button

Use the Standby Update Button to initiate the Primary to Standby program transfer.

 

You must have the keyswitch in transfer mode.

 

 

 

Note: If the controllers are given identical designations, the system refuses to

 

acknowledge them both. The first unit to power up will be recognized as the

 

Primary controller. It is designated A or B according to its switch position. The

 

second unit remains offline and the ComAct indicator flashes, indicating a startup

 

error.

 

 

 

 

 

Note: Once the system is running, Primary control may be exchanged between the

 

units regardless of which is designated as A or B.

 

 

 

 

20

840 USE 106 00 January 2003

Page 20