Schneider Electric 840 USE 106 0 manual Configuring 984 Hsby, Chs, Modsoft

Models: 840 USE 106 0

1 226
Download 226 pages 11.66 Kb
Page 70
Image 70

Using a Quantum 984 HSBY System

Configuring 984 HSBY

CHS software To configure a 984 HSBY system, you must load the CHS software into the controllers. The software is included on a diskette in the Hot Standby kit. Once you have loaded the software, you can choose how to proceed. You may control your Hot Standby system through ladder logic or you can use a configuration extension.

The CHS

The logic in the CHS loadable is the engine that drives the Hot Standby capability in

Loadable

a Quantum control system. The CHS loadable gives you the ability to:

specify the Hot Standby command register, which is used to configure and control Hot Standby system parameters

define a Hot Standby status register, which can be used to monitor the real

lmachine status of the system

implement a CHS instruction in ladder logic

Unlike HSBY (a comparable loadable used for Hot Standby configurations in 984 controllers), the CHS instruction does not have to be placed in a ladder logic program. However, the CHS software must be loaded into the Quantum controller in order for a Hot Standby system to be supported.

Installing the The following steps are only necessary if the CHS loadable is not already part of

CHS loadable your 984 installation. The CHS loadable is provided on a 3 1/2 diskette

into the 984 (140 SHS 945 00) as part of your 140 CHS 210 00 Hot Standby kit. The file is named

Environment QCHSVxxx.DAT, where xxx is the three-digit version number of the software.

Step

Action

1Insert the diskette in the disk drive.

2Either create a new Concept project or open an existing one and have a PLC selected

3With the menu command Project Configurator, open the configurator.

4With Configure Loadables, open the dialog box Loadables.

5Press the command button Unpack to open the standard Windows dialog box, Unpack Loadable File. Select the loadable file, click the button OK and it is inserted into the list box Available.

Modsoft

If you are using Modsoft, refer to the Modicon Quantum Hot Standby System

 

Planning and Installation Guide, 840 USE 106 00 Version 1, Paragraph 5.1.1.

 

 

70

840 USE 106 00 January 2003

Page 70
Image 70
Schneider Electric 840 USE 106 0 manual Configuring 984 Hsby, Chs, Modsoft