Schneider Electric 840 USE 106 0 manual LED Display, Module, CHS 110

Models: 840 USE 106 0

1 226
Download 226 pages 11.66 Kb
Page 19
Image 19

 

 

Overview of Quantum Hot Standby

 

 

LED Display

The following illustration shows five status indicators on the face of each CHS 110

 

module.

 

 

140

 

 

CHS 110 00

 

HOT STANDBY

 

Active

 

Ready

Fault

 

Run

Bal Low

 

Pwr ok

 

Modbus Com Err

Modbus! Error A

Com Act Error B

Primary

Mem Prt Standby

The following table shows the five status indicators.

Indicator

Color

Message

 

 

 

Ready

Green

If steady, power is being supplied to the module and it has

 

 

passed initial internal diagnostic tests. If blinking, module is

 

 

trying to recover from an interface error.

 

 

 

Com Act

Green

If steady, CHS 110 modules are communicating. If blinking, an

 

 

error has been detected.

 

 

 

Primary

Green

Module is Primary controller.

 

 

 

Com Err

Red

Module is retrying CHS communications or CHS

 

 

communications failure has been detected.

 

 

 

Standby

Amber

If steady, module is Standby controller, and is ready to assume

 

 

Primary role if needed. If blinking, program update is in

 

 

progress.

 

 

 

Error messages are discussed in detail in Com Act Error Patterns, p. 209.

840 USE 106 00 January 2003

19

Page 19
Image 19
Schneider Electric 840 USE 106 0 manual LED Display, Module, CHS 110, Following table shows the five status indicators