Maintenance

Detecting Failures in the Primary Backplane

Troubleshooting

 

To determine which component failed, compare the status of the controller, Hot

Components

 

Standby module and RIO head to the chart below:

 

 

 

 

 

 

Controller

CHS 110

RIO Head

Failure Type

Description

 

 

 

 

 

Stops

All LEDs off

All LEDs off except

READY on and

The Interface error patterns

 

except READY

READY

COM ACT blinks

are described in Com Act

 

OR COM ACT

 

four times

Error Patterns, p. 209

 

displays error

 

 

 

 

pattern

 

 

 

 

 

 

 

 

Runs as offline

All LEDs off

All LEDs off except

CHS 110

The Com Act error patterns

 

except READY

READY

 

are described in (See Com

 

OR COM ACT

 

 

Act Error Patterns, p. 209)

 

displays error

 

 

 

 

pattern

 

 

 

 

 

 

 

 

Stops

All LEDs off

All LEDs off except

RIO Head

The Com Act error patterns

 

except READY

READY OR COM

 

are described in Com Act

 

 

 

ACT displays error

 

Error Patterns, p. 209

 

 

 

pattern

 

 

 

 

 

 

 

Stops

All LEDs off

READY on and COM

RIO Cable Failure at

In a dual cable system, if only

 

except READY

ACT blinks four times

Primary End

one cable fails, the Error A or

 

 

 

 

 

Error B indicator on the RIO

 

 

 

 

 

head lights instead and the

 

 

 

 

 

system continues to operate.

 

 

 

 

 

When the RIO cable fails at

 

 

 

 

 

the Primary end, input data

 

 

 

 

 

may be reset to 0 for one

 

 

 

 

 

scan because the

 

 

 

 

 

communication failure to the

 

 

 

 

 

drop occurs before the

 

 

 

 

 

broken link is detected.

 

 

 

 

 

 

 

 

 

 

 

 

840 USE 106 00 January 2003

189