Using a Quantum 984 HSBY System

Transferring Additional State RAM Data

Additional Data If the Transfer Additional State RAM check box is activated, additional State RAM could be transferred.

In the Additional State RAM area, enter the number of 0x, 1x, 3x, and 4x data references that you want to be transferred as additional state RAM. All reference data items must be specified in multiples of 16. You must enter a value of 16 or greater for at least one of the four reference data types.

CAUTION

Transfer Additional State RAM Hazard

If you choose Transfer Additional State RAM, you must specify additional data to be transferred or the controller will not start.

Failure to follow this precaution can result in injury or equipment damage.

Use the Extra Transfer Time entry field to specify the number of scans over which you want the additional data to be transferred. In general, the system divides the number of reference data elements specified in the fifth entry field by the number of scans specified in the sixth entry field. Accordingly, it divides the data into groups that are transferred contiguously over the specified number of scans. These groups of data are transferred with the regular state RAM data that has been scheduled on every scan.

100

840 USE 106 00 January 2003

Page 100
Image 100