Using a Quantum IEC Hot Standby System

Specifying the Command Register

Bits in the Hot The command register controls various parameters of the Hot Standby system.

Standby

Command

Register

Disables keyswitch override = 0

Enables keyswitch override = 1

Sets Controller A to OFFLINE mode = 0

Sets Controller A to RUN mode = 1

Sets Controller B to OFFLINE mode = 0

Sets Controller B to RUN mode = 1

Forces standby offline if there is a logic mismatch = 0 Does not force standby offline if there is a logic mismatch = 1 (Supported only with Concept 2.5 or higher)

Allows exec upgrade only after application stops = 0 Allows exec upgrade without stopping application = 1 (Supported only with Concept 2.5 or higher)

0 = Swaps Modbus port 1 address during switchover

1 = Does not swap Modbus port 1 address on switchover

 

0 = Swaps Modbus port 2 address during switchover

 

1 = Does not swap Modbus port 2 address on switchover

 

0 = Swaps Modbus port 3 address during switchover

 

1 = Does not swap Modbus port 3 address on switchover

 

 

 

Note: Bit 16 in Modicon convention (shown in the diagram above) is bit 0 in IEC

 

convention. Setting bit 16 means writing a 0x0001 into the command register.

Specify

 

 

The command register is specified in the first entry field of the Hot Standby dialog.

Command

By default, the command register is set to 400001. If register 400001 is used

Register

elsewhere, enter another number greater than 0. The number you enter becomes

 

the 4x command register. For example, if you enter 14, the hot Standby command

 

register is 400014.

 

 

118

840 USE 106 00 January 2003

Page 118
Image 118
Schneider Electric 840 USE 106 0 manual Specifying the Command Register, Standby Command Register, Register is