Ethernet Hot Standby Solution

Step

Action

8The Secondary NOE now becomes the Primary NOE.

9Primary NOE opens all client connections and listens for all server connections and re-establishes those connections.

10Simultaneously, Secondary NOE listens for all server connections and re- establishes those connections.

Additional

The following list provides additional information about the NOE’s IP addressing

Switchover

process resulting from a Hot Standby switchover.

Information

 

 

 

 

Some MSTR/IEC Function blocks will not complete their transaction as a result

 

 

of the IP Address swap.

 

l

In this case, the MSTR/IEC Function block will return the error code 0x8000.

 

 

While the NOE is in the process of performing the above actions, a new MSTR/

 

 

IEC Function block may become active.

 

 

No resources are available to service the new MSTR/IEC Function block.

 

 

Therefore, the NOE will not service this new MSTR/IEC Function block, and all

 

 

three output lines will be low.

Going to Offline

 

When either the CPU stops or the Hot Standby state goes to offline mode, two

 

events occur:

 

1.

NOE mode goes to Offline

 

2.

NOE uses the IP Address of the present configuration

IP Address Assignment and Going Offline

HSBY State

IP Address Assigned Is ...

 

 

Primary to Offline

Configured IP Address, if other controller does not go to

 

Primary

 

 

Standby to Offline

Configured IP Address + 1

 

 

 

 

172

840 USE 106 00 January 2003