Image 107

Using a Quantum 984 HSBY System

The following diagram shows synchronizing time-of-day clocks.

Network 1 of Segment 1

40001

40101

CHS

4

40001 = Address of CHS Command Register

40101 = First Register Reserved for Nontransfer Area in State RAM 4 = Number of Registers Reserved in Nontransfer Area

Network 2 of Segment 1

 

 

 

0015

40103

42221

 

 

0

42221

0011

0002

0001

 

 

 

ADD

AND

SUB

TODC

TODC

42221

0001

42222

 

 

 

MBIT

MBIT

 

 

 

0001

0001

40103 = CHS Status Register

42221 = Mask Out Status Bits Not Required

42222 = Junk Register

TODC = Time-of-day Clock Register