Com Act Error Patterns

CRP Remote I/O Head Processor Error Patterns

Error Patterns The following table shows error patterns.

 

Number

Code

Error

 

Blinks

 

 

 

 

 

 

 

Slow (steady)

0000

requested kernel mode

 

 

 

 

 

2

6820

hcb frame pattern error

 

 

 

 

 

2

6822

head control block diag error

 

 

 

 

 

2

6823

mod personality diag error

 

 

 

 

 

2

682A

fatal start IO error

 

 

 

 

 

2

682B

bad read IO pers request

 

 

 

 

 

2

682C

bad execute diag request

 

 

 

 

 

2

6840

ASCII input xfer state

 

 

 

 

 

2

6841

ASCII output xfer state

 

 

 

 

 

2

6842

IO input comm state

 

 

 

 

 

2

6843

IO output comm state

 

 

 

 

 

2

6844

ASCII abort comm state

 

 

 

 

 

2

6845

ASCII pause comm state

 

 

 

 

 

2

6846

ASCII input comm state

 

 

 

 

 

2

6847

ASCII output comm state

 

 

 

 

 

2

6849

building 10 byte packet

 

 

 

 

 

2

684A

building 12 byte packet

 

 

 

 

 

2

684B

building 16 byte packet

 

 

 

 

 

2

684C

illegal IO drop number

 

 

 

 

 

3

6729

984 interface bus ack stuck high

 

 

 

 

 

4

6616

coax cable initialization error

 

 

 

 

 

4

6617

coax cable dma xfer error

 

 

 

 

 

4

6619

coax cable dumped data error

 

 

 

 

 

4

681A

coax cable DRQ line hung

 

 

 

 

 

4

681C

coax cable DRQ hung

 

 

 

 

 

5

6503

RAM address test error

 

 

 

 

 

6

6402

RAM data test error

 

 

 

 

 

7

6300

PROM checksum error (exec not loaded)

 

 

 

 

 

7

6301

PROM checksum error

 

 

 

 

 

8

8001

kernel PROM checksum error

 

 

 

 

 

 

 

 

840 USE 106 00 January 2003