User Defined Option

User Defined

State RAM

Transfer

The User Defined option lets you specify the amount of each reference data type that you want to be transferred on each scan. If the Transfer Additional State RAM check box is activated, it allows you to transfer additional data.

000001

Outputs transferred

000002

on every scan

000003

 

 

Remaining outputs

0nnnnn

not transferred

100001

Inputs transferred

100002

on every scan

100003

 

1nnnnn

Remaining inputs

not transferred

300001

Inputs transferred

300002

on every scan

300003

 

 

Remaining inputs

3nnnnn

not transferred

400001

 

400002

Outputs transferred

400003

on every scan

400004

 

400005

 

400006

 

Remaining outputs not transferred

4nnnnn

Use the State RAM area to define the size of the data range. All of the reference data that you specify in this area is transferred from the Primary to the Standby controller on every scan (except the defined nontransfer area). All reference data items must be 0 or specified in multiples of 16. A minimum of 16 4x registers is required. The maximum amount of state RAM to be transferred on every scan can be as much as the total amount of available state RAM (10K, 32K, or 64K, depending on the type of Quantum controller).

840 USE 106 00 January 2003

99