Maintenance

Detecting Failures in a Hot Standby System

Main

If one of the main components of the Primary backplane fails, control shifts to the

Components of

Standby. If a component fails in the Standby backplane, the Standby goes offline.

the Primary

Likewise, if the fiber cable link between the Hot Standby modules fails, the Standby

Backplane

goes offline.

 

This section helps you determine which component failed. When you have replaced

 

that component, you must cycle power, with one exception. After cycling power, if

 

the backplane is now operating, it assumes the Standby role. If the failure was in the

 

fiber cable, the backplane may return to Standby mode without cycling power.

 

If replacing the component does not solve the problem, call Schneider Electric

 

customer support at 1-800-468-5342 for further directions.

 

 