Using a Quantum IEC Hot Standby System

 

 

 

 

 

 

 

Options for

Option 1

 

 

 

 

Software Control

 

 

 

 

 

Stage

Description

 

Comment

 

Example

 

 

 

 

 

 

 

1

Change the setting on the Hot

 

To do this, you must shut down the

 

 

 

 

 

 

Standby dialog.

 

system and make the necessary change

 

 

 

 

 

in the dialog, then power up the system

 

 

 

 

 

again.

 

 

 

 

 

 

 

 

2

Download the new configuration.

 

 

 

 

 

 

 

 

 

 

Option 2

 

 

 

 

 

 

 

 

 

 

 

Stage

Description

 

Comment

 

 

 

 

 

 

 

 

1

Connect Concept to your Primary

 

 

 

 

 

controller.

 

 

 

 

 

 

 

 

 

 

2

Call up the Reference Data Editor

 

 

 

 

 

(RDE).

 

 

 

 

 

 

 

 

 

 

3

Place the Hot Standby command

 

The operating mode of controller B is

 

 

 

register and the Hot Standby status

 

determined by the state of bit 14 of the

 

 

 

register in the RDE.

 

command register. If controller B is

 

 

 

 

 

offline, bit 14 is set to 0.

 

 

 

 

 

 

 

 

4

To put the controller in RUN mode,

 

Controller B immediately goes into RUN

 

 

 

change the state of bit 14 to 1.

 

mode.

 

 

 

 

 

 

 

Note: The advantage of option 2 is that the Hot Standby system does not have to be

 

 

shut down in order to change its status.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

840 USE 106 00 January 2003

121

Page 121
Image 121
Schneider Electric 840 USE 106 0 manual Options for, Software Control, Stage Description Comment