Ethernet Hot Standby Solution

IP Address Assignment

Configuring the

The NOE can be configured to work in conjunction with the Hot Standby controller.

NOE

Since the Primary and Secondary controllers must have an identical configuration,

 

the configured IP Addresses will be the same. The NOE’s IP Address is either the

 

configured IP Address or the configured IP Address +1. The IP Address is

 

determined by the current local Hot Standby state.

 

In the Offline state, the IP Address is determined by whether or not the other

 

controller is in transition to the Primary state.

 

 

 

 

Note: For a Hot Standby system, the two IP Addresses will be consecutive.

 

 

 

 

The following table shows the IP Address assignments.

 

 

 

 

Hot Standby State

IP Address

 

 

 

 

Primary

Configured IP Address

 

 

 

 

Standby

Configured IP Address + 1

 

 

 

 

Transition from Primary to Offline

Configured IP Address, if peer controller does not

 

 

go to Primary

 

 

 

 

Transition from Standby to Offline

Configured IP Address + 1

 

 

 

 

 

 

Note: Offline - Results depend on whether or not the other controller is detected as

 

in transition into the primary state. If Current IP is the configured IP Address, then

 

change the IP Address to the configured IP Address + 1.

IP Address

 

 

 

 

For continued Ethernet communication, the new Primary NOE must have the same

Transparency

IP Address as the former Primary NOE. The IP Address in the Secondary NOE (an

 

NOE in the secondary state) is IP Address + 1.

 

The NOEs integrated in the Hot Standby configuration coordinate this swapping IP

 

Address with the management of Ethernet services used.

 

 

 

Note: Do not use the address IP + 1. For a Hot Standby system, do not use

 

consecutive addresses of the configured IP Address. If you configure the last IP

 

Address (255), NOE returns diagnostic code "Bad IP configuration".

 

 

 

 

 

 

168

840 USE 106 00 January 2003

Page 168
Image 168
Schneider Electric 840 USE 106 0 manual IP Address Assignment, Configuring, Transparency