Using a Quantum IEC Hot Standby System
122 840 USE 106 00 January 2003

Advanced Options Concept 2.5

Advanced
Options button When selecting the Advanced Options butt on in the Hot Standby dialog you get the
opportunity to allow different firmware versions on the Primary and Standby
controller while running in full Hot Standby mode.
This lets you upgrade the controllers step by step to a new firmware version w ithout
having to shutdown the system. Since this is only necessary in rare situations, it is
recommended that you disable this mode by configuration and to enable it by the
reference data editor when needed. By default, the controllers must have the same
versions of firmware. This means the Standby controller would not go online while
having a newer or older firmware version than the one on the Primary controller.
Note: This option is available only in Hot Standby systems already running with
Concept 2.5.
Advanced Options
WARNING!!
Selecting “Without Stopping” overrides
all safety checking between
Primary and Hot Standby controllers.
Use with extreme caution!!!
Exec Upgrade
Without Stopping
Application Stopped
OK Cancel Help