Using a Quantum IEC Hot Standby System

Advanced Options Concept 2.5

Advanced

When selecting the Advanced Options button in the Hot Standby dialog you get the

Options button

opportunity to allow different firmware versions on the Primary and Standby

 

controller while running in full Hot Standby mode.

 

Advanced Options

WARNING!!

Selecting “Without Stopping” overrides all safety checking between

Primary and Hot Standby controllers. Use with extreme caution!!!

Exec Upgrade

Without Stopping

Application Stopped

OK

Cancel

Help

This lets you upgrade the controllers step by step to a new firmware version without having to shutdown the system. Since this is only necessary in rare situations, it is recommended that you disable this mode by configuration and to enable it by the reference data editor when needed. By default, the controllers must have the same versions of firmware. This means the Standby controller would not go online while having a newer or older firmware version than the one on the Primary controller.

Note: This option is available only in Hot Standby systems already running with Concept 2.5.