Using a Quantum IEC Hot Standby System

IEC HSBY

System

Executive

Upgrade

Procedure

The following table shows the steps to upgrade the controller’s executive in an IEC HSBY system. Note: You must first have both controllers running in Concept 2.5.

Step

Action

 

 

 

 

1

Connect to the Primary controller with Concept and use the reference data editor

 

 

to set bit 12 of the Hot Standby command register to 1.

 

 

 

 

2

Disconnect from the Primary controller.

 

 

 

 

3

Use the Executive Loader to download the new executive to the Standby

 

 

controller.

 

 

 

 

4

Connect to the Standby controller with Concept and download the project.

 

 

NOTE: Projects developed with versions of Concept earlier than 2.5 must be

 

 

imported into Concept 2.5 using the Converter.

 

 

 

 

5

Start the Standby controller.

 

 

 

 

6

Verify that the Standby controller is in Run Mode and the CHS module indicates

 

 

that the Standby Controller is now in Standby mode.

 

 

 

 

7

Disconnect from the controller.

 

 

 

 

8

Initiate a Hot Standby switchover using the Key Switch.

 

 

 

 

9

Download the Executive to the new Standby Controller using the Executive

 

 

loader.

 

 

 

 

10

Use the transfer button on the CHS module to transfer the program to the

 

 

Standby controller. Verify that the Standby controller is in Run Mode and the

 

 

CHS mode indicates that the Standby Controller is now in Standby Mode.

 

 

 

 

11

The Hot Standby Controller Executives have now been uprgaded without

 

 

stopping the process.

 

 

 

 

 

 

 

840 USE 106 00 January 2003