26 en Power Supply and Power OutputsControl Panel

4.6.4Terminal 8

Terminal 8 provides continuous positive (+) 12.0 VDC Nominal power. Output C interrupts the power at Terminal 8 when activated. Use Terminal 8 to power smoke detectors or other devices that are reset by interrupting power. One self-resetting circuit breaker protects Terminals 6, 7, and 8 against shorts.

Verification/Reset Output

The default program sets Output C (Terminal 8) as a verification and reset output. Refer to Output Parameters and Point Assignments in the D9412GV4/D7412GV4 v2.00 Program Entry Guide (P/N: F01U265459) for instructions on programming verification/reset outputs and points.

Performing a sensor reset at a keypad produces a five-second output activation of verification/ reset outputs. The control panel ignores verification and reset points during the five-second output activation.