Control PanelPower Supply and Power Outputs en 21
| D8004 Transformer Enclosure Required for Fire Systems |
| Use the D8004 Transformer Enclosure for the D1640 Transformer in fire and combined fire |
| and burglary applications. |
|
|
i | Notice! |
Check with the Authority Having Jurisdiction (AHJ) about mounting transformers on specific | |
| circuits. |
|
|
4.2 | Power Terminals - Secondary |
4.2.1 | Secondary (DC) Power |
| A 12 V, 7 Ah (up to 18 Ah) sealed |
| auxiliary and alarm outputs, and powers the system during interruptions in primary (AC) |
| power. |
Warning!
!Use Lead Acid Batteries Only: The charging circuit is calibrated for
Extra Batteries Increase
To increase battery
D1218 Battery
The D1218 is a 12 V, 18 Ah battery for use in applications requiring extended battery standby time. Up to two D1218 batteries can be connected when used with a D122 Dual Battery Harness.
Warning!
!When connecting two D1218 Batteries to the control panel, the control panel can charge up to 36 Ah of battery.
i | Notice! |
When using two D1218 batteries, use a separate enclosure, a D122L Dual Battery Harness, | |
| and long leads. |
|
|
4.2.2 | Installing the Battery |
1.Place the battery upright in the base of the enclosure.
2.Locate the red and black leads supplied in the literature pack.
3.Connect the black battery lead to Terminal 4, and then to the negative
4.Connect the red battery lead to Terminal 5, and then to the positive (+) side of the battery.