20 en Power Supply and Power OutputsControl Panel
4 | Power Supply and Power Outputs |
|
| ||
4.1 | Power Supply - Primary |
|
|
| |
4.1.1 | Primary (AC) Power Circuit |
|
|
| |
| The primary source is a 16.5 VAC, 40 VA, | ||||
| Systems, Inc. Model D1640). The control panel draws 225 mA when idle and 300 mA when in | ||||
| an alarm state. The total available auxiliary current is 1.4 A. Transient suppressors and spark | ||||
| gaps protect the circuit from power surges. This protection relies on the ground connection at | ||||
| Terminal 10. Ensure that you connect Terminal 10 to a proper ground. Refer to Connecting | ||||
| Earth Ground, page 7. |
|
|
| |
| AC Power Fail |
|
|
|
|
| The system indicates an AC power failure when Terminals 1 and 2 do not have power. The AC | ||||
| Fail Time parameter sets the number of minutes or seconds without AC power before the | ||||
| control panel acknowledges the failure and the number of minutes or seconds after the power | ||||
| returns before the control panel acknowledges restored power. |
| |||
| Refer to the D9412GV4/D7412GV4 v2.00 Program Entry Guide (P/N: F01U265459) for | ||||
| additional information about AC Fail Time and UL 864 requirements. |
| |||
| Reference the table below to view the Modem4 communication format signals. | ||||
|
|
|
|
|
|
Modem4 Events |
| Modem4 code | Modem4 Code | Contact ID | Contact ID Codes |
|
| D6500 Mode | Bosch SIA Mode | Events |
|
|
|
|
|
| |
AC Fail - mains power supply | Pssss | NAT | AC Loss | 1 301 00 000 | |
|
|
|
|
| |
AC Restore - mains power supply | Rsss0 | NAR | AC Loss | 3 301 00 000 | |
|
|
|
|
| |
Table 4.1: AC Power Fail |
|
|
|
| |
4.1.2 | Installing the Transformer |
|
|
| |
|
|
|
|
|
|
| Notice! |
|
|
|
|
i | Do not | |
nal fuse, causing permanent failure. Connect the transformer to Terminals 1 and 2 of the con- | ||
| ||
| trol panel before plugging it into the power source. |
1.Use 18 AWG (1.22 mm) wire (minimum) to connect the transformer to the control panel. The wire length should be as short as possible. The maximum length is 50 ft (15 m). Connect the battery and plug in the transformer.
2.Route telephone and sensor loop wiring away from any AC conductors, including the transformer wire.
AC wiring can induce noise and low level voltage into adjacent wiring. Route data wiring away from AC and telephone wiring.
i | Notice! | |
Always connect the battery first and then plug in the transformer. | ||
|
3.Connect the battery. Refer to Installing the Battery, page 21
4.Plug the transformer into an unswitched, 120 VAC 60 Hz power outlet only.
5.Secure the transformer to the outlet with the screw provided.
2012.12 02 F.01U.265.462 | UL Installation Instructions | Bosch Security Systens, Inc. |