30 en SpecificationsControl Panel
|
|
|
| Recharge Cycle | AC ON – Load shed relay resets, battery charging |
|
|
|
|
| begins, Battery Trouble and AC Restoral Reports |
|
|
|
|
| sent. |
|
|
|
|
|
|
|
|
|
|
| 12.6 VDC – Battery Restoral Report sent, Low |
|
|
|
|
| Battery LED off. |
|
|
|
|
|
|
|
| Environmental | Temperature: | +32゚F to +120゚F (0゚C to +49゚C) | |
|
|
|
|
|
|
|
|
|
| Relative | Maximum 93% |
|
|
|
| Humidity: |
|
|
|
|
|
|
|
|
| Compatible | D8103 Universal Enclosure (requires B12 mounting plate), D8108A | ||
|
| Enclosures | Attack Enclosure (requires B12 mounting plate), B10 Enclosure, | ||
|
|
|
| D8004 Transformer Enclosure, D2203 Enclosure, | |
|
|
|
| ||
|
|
|
| Enclosures |
|
|
|
|
|
|
|
|
| Table 5.1: B520 Specifications |
| ||
5.2 |
| Terminal Wiring Requirements | |||
|
|
|
|
| |
Terminal | Terminal | Requirements |
|
| |
No | Description |
|
|
| |
|
|
| |||
1 | AC | 18 AWG min (up to 14 AWG max) | |||
|
|
| |||
2 | AC | 18 AWG min (up to 14 AWG max) | |||
|
|
| |||
3 | + AUX POWER | Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current. | |||
|
|
| |||
4 | BATTERY - | Bosch supplied wire lead, included with panel. | |||
|
|
| |||
5 | BATTERY + | Bosch supplied wire lead, included with panel. | |||
|
|
| |||
6 | OUTPUT A | Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current. | |||
|
|
| |||
7 | OUTPUT B | Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current. | |||
|
|
| |||
8 | OUTPUT C | Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current. | |||
|
|
| |||
9 | COMMON | Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current. | |||
|
|
|
|
| |
10 | EARTH | 14 to 16 AWG |
|
| |
| GROUND |
|
|
| |
|
|
| |||
11 | POINT 1 | Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop | |||
|
|
| resistance less than 100 Ω. |
| |
|
|
| |||
12 | POINT 1/2 | Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop | |||
| COMMON | resistance less than 100 Ω. |
| ||
|
|
| |||
13 | POINT 2 | Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop | |||
|
|
| resistance less than 100 Ω. |
| |
|
|
| |||
14 | POINT 3 | Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop | |||
|
|
| resistance less than 100 Ω. |
| |
|
|
| |||
15 | POINT 3/4 | Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop | |||
| COMMON | resistance less than 100 Ω. |
| ||
|
|
|
|
|
|
2012.12 02 F.01U.265.462 | UL Installation Instructions | Bosch Security Systens, Inc. |