Terminal Wiring Requirements

30 en SpecificationsControl Panel

 

 

 

 

Recharge Cycle

AC ON – Load shed relay resets, battery charging

 

 

 

 

 

begins, Battery Trouble and AC Restoral Reports

 

 

 

 

 

sent.

 

 

 

 

 

 

 

 

 

 

 

12.6 VDC – Battery Restoral Report sent, Low

 

 

 

 

 

Battery LED off.

 

 

 

 

 

 

 

 

Environmental

Temperature:

+32F to +120F (0C to +49C)

 

 

 

 

 

 

 

 

 

 

Relative

Maximum 93% non-condensing

 

 

 

 

Humidity:

 

 

 

 

 

 

 

 

 

Compatible

D8103 Universal Enclosure (requires B12 mounting plate), D8108A

 

 

Enclosures

Attack Enclosure (requires B12 mounting plate), B10 Enclosure,

 

 

 

 

D8004 Transformer Enclosure, D2203 Enclosure, BATB-80 Enclosure,

 

 

 

 

BATB-40 Enclosure (requires B12 mounting plate), AE1, AE2

 

 

 

 

Enclosures

 

 

 

 

 

 

 

 

 

Table 5.1: B520 Specifications

 

5.2

 

Terminal Wiring Requirements

 

 

 

 

 

Terminal

Terminal

Requirements

 

 

No

Description

 

 

 

 

 

 

1

AC

18 AWG min (up to 14 AWG max)

 

 

 

2

AC

18 AWG min (up to 14 AWG max)

 

 

 

3

+ AUX POWER

Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current.

 

 

 

4

BATTERY -

Bosch supplied wire lead, included with panel.

 

 

 

5

BATTERY +

Bosch supplied wire lead, included with panel.

 

 

 

6

OUTPUT A

Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current.

 

 

 

7

OUTPUT B

Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current.

 

 

 

8

OUTPUT C

Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current.

 

 

 

9

COMMON

Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current.

 

 

 

 

 

10

EARTH

14 to 16 AWG

 

 

 

GROUND

 

 

 

 

 

 

11

POINT 1

Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop

 

 

 

resistance less than 100 Ω.

 

 

 

 

12

POINT 1/2

Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop

 

COMMON

resistance less than 100 Ω.

 

 

 

 

13

POINT 2

Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop

 

 

 

resistance less than 100 Ω.

 

 

 

 

14

POINT 3

Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop

 

 

 

resistance less than 100 Ω.

 

 

 

 

15

POINT 3/4

Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop

 

COMMON

resistance less than 100 Ω.

 

 

 

 

 

 

 

2012.12 02 F.01U.265.462