24 en Power Supply and Power Outputs | Control Panel |
|
|
–Terminal 8: Output C (Switched Auxiliary Power) PTC CB5 protects Terminal 24: Zonex Power.
PTC CB1 protects Terminal 32: SDI Power +.
PTC CB3 protects Terminal 36: SDI2 Power +.
Required by UL:
–All devices powered from a power output are to be supervised.
–Power outputs are not shared between fire and
4.4 | Power Outputs - Total Available Power |
The system produces up to 1.4 A of combined power at 12.0 VDC Nominal for all powered devices. The outputs listed below share the available power. These outputs are shown as red circles on the faceplate.
–Terminal 3 - Auxiliary Power. Use this terminal to power devices requiring continuous power.
–Terminal 6 (Output A) - Alarm Power Output. Programmable relay normally open, power on alarm.
–Terminal 7 (Output B) - Alternate Alarm Power Output. Programmable relay normally open, power on alarm.
–Terminal 8 (Output C) - Switched Auxiliary Power. Programmable relay normally closed, switches power off when the Sensor Reset command is executed.
–Terminal 24 - Zonex Power. Use this terminal to power Zonex modules such as the D8125, D8128D, and D8129 Modules.
–Terminal 32 - SDI Power +. Use this terminal to power serial device interface (SDI) devices such as keypads, the D9210C Wiegand Control Interface Module, the ICP-
–Terminal 36 - SDI2 Power +. Use this terminal to power serial device interface 2 (SDI2) devices such as B208, B308, B426, B810, B920, B930, and other compatible SDI2 devices.
4.5 | Power Outputs - Continuous Power Output Terminals 3, 8, 24, |
| 32, and 36 |
| The continuous current draw for powered devices connected to Terminals 3, 8, 24, 32, and 36, |
| and the accessory connector must not exceed 1.4 A. Devices powered from these outputs |
| must operate at 12.0 VDC Nominal. |
| Power Restricted for Fire and Combined Fire and Burglary Systems |
| Use the Fire System Power Formula to calculate the current available for fire and combined |
| fire and burglary systems (refer to Power Outputs - Programmable Power Output Terminals 6, 7, |
| and 8, page 24). |
4.6 | Power Outputs - Programmable Power Output Terminals 6, 7, |
| and 8 |
4.6.1 | Programming |
| The power outputs at Terminals 6, 7, and 8 are programmed as Outputs A, B, and C. All |
outputs are programmed in the Outputs section. Outputs are assigned a output type, (Fire Bell, for example) when they are assigned to an area. Outputs can be assigned to one or more areas. The Bosch defaults set Output A (Terminal 6) as a Steady Alarm Bell output, Output B (Terminal 7) as a Pulsed Fire Bell output, and Output C (Terminal 8) as a Verification or Reset output for smoke detectors. The D9412GV4/D7412GV4 v2.00 Program Entry Guide (P/N:
2012.12 02 F.01U.265.462 | UL Installation Instructions | Bosch Security Systens, Inc. |