Bosch Appliances D9412GV4 4.6.2, Terminals 6 and, 4.6.3, Fire System Power Formula

Models: D9412GV4

1 36
Download 36 pages 16.55 Kb
Page 25
Image 25
Voltage Output at Terminals 6, 7, and 8

Control Panel

Power Supply and Power Outputs en 25

 

 

F01U265459) contains complete instructions for programming outputs. Refer to Terminals 6 and 7, page 25, Fire System Power Formula, page 25, and Terminal 8, page 26 for descriptions of the functions of each terminal. Refer to the Bell Parameters section of the program to set the Fire Bell, Alarm Bell, and Gas Bell output responses for outputs. Four annunciation patterns are available: Steady, Pulsed, California Standard, Temporal Code 3, and Temporal Code 4.

Voltage Output at Terminals 6, 7, and 8

If Terminals 6, 7, and 8 do not provide the expected output, check:

Programming for Outputs A, B, and C in the outputs section of the program. For proper operation, do not program a Panel Wide Output the same as an Area Wide Output.

Bell Parameters section of the program to confirm that the Alarm, Fire, and Gas Bell responses are programmed for the expected duration and pattern.

Point Assignments section to confirm that each point is programmed for the expected local response.

4.6.2

Terminals 6 and 7

 

When activated, Terminals 6 (Output A) and 7 (Output B), provide positive (+) 12.0 VDC

 

Nominal power output. Use the power at Terminals 6 and 7 to power bells, siren drivers,

 

piezoelectric fire sounders, electronic horns, or other devices.

 

Programming determines the format of the output and the conditions that activate it. One self-

 

resetting circuit breaker protects Terminals 6, 7, and 8 against shorts. When using Output A or

 

Output B to activate notification appliance circuits in UL Listed fire alarm applications, install

 

a D192G Indicating Circuit Module.

 

Available Power

 

The system combines the 1.4 A of primary power produced by the power supply with the

 

secondary power source (the battery) to produce a total of 2.0 A of alarm power at 12.0 VDC

 

Nominal. Terminals 6 and 7 share the available alarm power.

 

Power Restricted for Fire and Combined Fire and Burglary Systems

 

Fire systems are prohibited from using the battery for determining alarm power. Use the fire

 

system power formula described in Fire System Power Formula, page 25 to calculate the

 

current available for fire and combined fire and burglary systems.

4.6.3

Fire System Power Formula

 

To calculate the current available at Terminals 6 and 7 for fire and combined fire and burglary

 

systems:

 

1.

Add together the current draws for all devices connected to Terminals 3, 8, 24, and 32,

 

 

and the accessory connector. This is the total current required for the normal standby

 

 

condition (NSC).

 

2.

The current available for NSC is 1.4 A. Subtract the NSC current required calculated in

 

 

Step 1 from the NSC current available, 1.4 A. The difference is the alarm current available

 

 

for Terminals 6 and 7.

In formula format:

1.4 A - NSC current required (Step 1) = Alarm current available

Refer to the Approved Applications chapter inside the D9412GV4/D7412GV4 v2.00 Installation and System Reference Guide (P/N: F01U265457) for module or accessory current requirements.

Bosch Security Systens, Inc.

UL Installation Instructions

2012.12 02 F.01U.265.462

Page 25
Image 25
Bosch Appliances D9412GV4 4.6.2, Terminals 6 and, 4.6.3, Fire System Power Formula, Voltage Output at Terminals 6, 7, and