IGNITION CONTROL MODULE
The interrupted proved ignition device conserves energy. When additional heat is needed, the combustion air blower starts to purge all air from the combustion chamber for about 15 seconds. On proof of air flow, the air proving switch closes and the igniter is energized, eliminating the fuel costs of maintaining a constant pilot. To assure safe operation, the gas valve cannot open until the pilot igniter is verified. The 100% igniter safety is an electronic device which closes the main gas valve within 8/10 of a second whenever the flame is interrupted. Main burner is automatically lit when the device is powered and
Fig #9322
IGNITIONMODULE
HIGH LIMIT (MANUAL RESET)
The heater is equipped with a manual reset high limit temperature device. Push the reset button and adjust the setting to 30° F or 40° F above desired operating temperature.
Drw. #8644
Fig.
MANUAL RESET HIGH LIMIT
FLOW SWITCH
Flow switch will not operate if flow is less than 20 GPM.
OPERATING CONTROL
Drw. #8241.1
Fig.
FLOW SWITCH
The heater may be equipped with different types of operating controls. Consult data sheet supplied with installation instructions. See Section L for adjustment safety precautions on domestic hot water applications.
Drw. #8643
THERMOSTATCONTROL