Raypak 122-322 installation instructions SECTION J-5, Outdoor Installation

Models: 122-322

1 56
Download 56 pages 23.48 Kb
Page 37
Image 37
SECTION J-5

SECTION J-5

Outdoor Installation

Outdoor models are self-venting when installed with the factory-supplied restricted direct vent cap and require no additional vent piping. This special vent cap is provided with the heater in accordance with CSA requirements. It must be installed directly on the heater. See Section B for correct clearances.

Care must be taken when locating the outdoor unit because the flue gases discharged from the vent hood can condense as they leave the hood. Improper location can result in damage to adjacent structures or building finish. For maximum efficiency and safety, the following precautions must be observed:

a)Outdoor models must be installed outdoors and must use the outdoor vent hood supplied by the manufacturer.

b)Periodically check venting system. The heater’s venting areas must never be obstructed in any way and minimum clearances must be observed to prevent restriction of combustion and ventilation air. Keep area clear and free of combustible and flammable materials.

c)Do not locate adjacent to any window, door walkway, or gravity air intake. The vent must be located a minimum of four (4) feet horizontally, or four (4) feet below, or one (1) foot above such areas.

d)Install above grade level and above normal snow levels.

e)Vent terminal must be at least 3 feet above any forced air inlet located within 10 feet.

f)Adjacent brick or masonry surfaces must be protected with a rust-resistant sheet metal plate.

g)Multiple Outdoor Vent installations require a four (4) feet clearance between vent caps.

NOTICE:

Condensate can freeze on the vent cap. Frozen condensate on the vent cap can result in a blocked flue condition.

The restricted vent cap must be furnished by the heater manufacturer in accordance with its listing.

An outdoor air filter, supplied by the manufacturer is mounted on the heater.

37

Page 37
Image 37
Raypak 122-322 installation instructions SECTION J-5, Outdoor Installation