3.0START-UP

3.1Blower Adjustment

1.Disconnect fan pressure switch tubing at plenum and connect manometer using a tee.

2.Close all manual firing valves.

3.Turn power on;

4.Check manometers attached to fan pressure switch. The readings should be :

.5 + .1” W.C. for models 102 and 122

.7 + .1” W.C. for models 202, 242, 322

If not, adjust the air shutter on the blower to attain the correct value. (See air shutter adjustment page 7)

5.Turn power off.

6.Reconnect fan pressure switch tubing to original position.

3.2Main Burner Adjustment

1.Turn off unit.

2.Open manual firing valve.

3.Turn on the unit, wait 15 seconds, and the igniter should glow. Sight glass to check igniter at both ends of the heater. Gas valve should be open after 45 seconds.

4.If burner does not light on first trial. It will retry, up to 3 times

5.Main burner ignition – check manifold gas pressure at gas valve manifold pressure tap. (See gas valve detail page 7) This should read 3.5 + .1” W.C. for natural gas or 10.5 + .1” W.C. for LP gas.

6.If the pressure reading differs by more than + .1" W.C. Remove manifold adjustment screw cover off the pressure regulator on the gas valve, adjust main burner manifold pressure. Replace the manifold adjustment screw cap on the gas valve.

Your Hi Delta is tuned in!

3.3Safety Inspection

Replace main gas manifold adjustment screw cap.

Check all thermostats and high limit settings.

During the following safety checks leave manometers hooked up, check and record.

If other gas fired equipment are in the room and on same gas main check all pressures on the Hi Delta with all other equipment running.

Remember, incoming gas pressure could be lower than specified on page 19, provided 3.2.5 is met.

Check thermostats for ON/OFF operation.

Check High limits for ON/OFF operation.

While in operation, check flow switch operation

Check the low gas pressure switches (For proper adjustment, if available, use the attached manometers to set pressure. The scales on the switch are approximate only ); Low gas pressure switch must be set at 5" W.C. for natural gas and 10” W.C. for LP gas.

High gas pressure switch (optional) at 1" W.C. above manifold pressure.

Insert ignition control lockout tests as safety check.

3.4Follow-Up

Safety checks must be recorded as performed.

Turn unit on.

After main burner ignition:

Check Manometer for proper reading.

Cycle unit several times and recheck readings

Reanalyze with unit running record or print results.

Remove all Manometers and replace hose, remove jumper, replace all gas pressure caps.

Check for gas leaks one more time.

45

Page 45
Image 45
Raypak 122-322 installation instructions Start-Up, Your Hi Delta is tuned

122-322 specifications

Raypak 122-322 is a cutting-edge pool and spa heater designed for optimal performance and efficiency. Known for its robust construction and reliable heating capabilities, this heater has become a preferred choice among pool owners.

One of the standout features of the Raypak 122-322 is its advanced copper fin tube heat exchanger. This innovative technology enhances the heater's efficiency by maximizing heat transfer while minimizing energy consumption. By efficiently circulating the water through the heat exchanger, the Raypak 122-322 quickly raises the temperature, allowing for an enjoyable swimming experience regardless of the weather.

The heater is equipped with a digital control system that allows for precise temperature adjustments. This user-friendly interface makes it easy to set and maintain the desired water temperature, promoting user convenience. The digital controls also provide diagnostic features, which simplify troubleshooting and maintenance, ensuring the heater operates smoothly for years to come.

Safety is a crucial aspect of the Raypak 122-322. It comes with a series of safety features, including a flame rollout switch, high limit switch, and a pressure switch that ensures the unit operates safely under various conditions. This focus on safety provides peace of mind for users, knowing that their heating system is designed with protective measures in place.

The Raypak 122-322 is environmentally friendly, designed to use less energy compared to conventional heating systems. Its efficient performance not only reduces operational costs but also lessens the overall environmental impact, making it a responsible choice for conscious consumers.

With a compact design, the Raypak 122-322 can fit easily into various installation spaces, making it versatile for numerous residential or commercial settings. Additionally, the unit is built with durable materials resistant to corrosion and weather conditions, ensuring longevity and minimal maintenance requirements.

Overall, the Raypak 122-322 stands out in the market due to its advanced features, safety mechanisms, energy efficiency, and ease of use. It exemplifies a perfect blend of innovation and reliability, making it an exceptional option for anyone looking to enhance their pool or spa experience.