Raypak 122-322 Section H Gas Supply Connections, Danger, Gas Supply Pressure

Models: 122-322

1 56
Download 56 pages 23.48 Kb
Page 19
Image 19
SECTION H: GAS SUPPLY CONNECTIONS

SECTION H: GAS SUPPLY CONNECTIONS

DANGER:

Make sure the gas on which the heater will operate is the same type as specified on the heater model and rating plate.

Gas piping must have a sediment trap ahead of the heater gas controls, and a manual shut-off valve located outside the heater jacket. A pounds to inches regulator must be installed to reduce to gas supply pressure to under 14" W.C. The regulator should be placed a minimum distance of 10 times the pipe diameter upstream of the heater gas controls. All gas piping must be tested after installation in accordance with local codes. The heater and its gas connection must be leak-tested before placing it in operation.

Fig. #9401.1

GAS SUPPLY CONNECTION

CAUTION:

The heater and its manual shutoff valve must be disconnected from the gas supply during any pressure testing of the gas supply system at test pressures in excess of 1/2 PSIG (3.45 KPA). The heater must be isolated from the gas supply piping system by closing the manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG. Relieve test pressure in the gas supply line before reconnecting the heater and its manual shut off valve to the gas supply line. FAILURE TO FOLLOWTHIS PROCEDURE MAY DAMAGE THE GAS VALVES. Over pressurized gas valves are not covered by warranty. The heater and its gas connections shall be leak tested before placing the appliance in operation. Use soapy water for leak test: DO NOT use open flame.

CAUTION:

CAUTION:

Do not use Teflon tape on gas line pipe thread. A pipe compound rated for use with gas systems is recommended. Apply sparingly only on male pipe ends.

Support gas supply piping with hangers, not by the heater or its accessories. Ensure the gas piping is protected from physical damage and freezing where required.

GAS SUPPLY PRESSURE

A minimum of 7” W.C. and a maximum of 10.5” W.C. upstream gas pressure is required under no load conditions for natural gas. A minimum of 12” W.C. and a maximum of 13” W.C. is required for propane gas. The gas pressure regulator supplied on the heater is for low pressure service. If upstream pressure exceeds 14" W.C, an intermediate gas pressure regulator, of the lockup type, must be installed.

When connecting additional gas utilization equipment to the gas piping system, the existing piping must be checked to determine if it has adequate capacity.

19

Page 19
Image 19
Raypak 122-322 installation instructions Section H Gas Supply Connections, Danger, Gas Supply Pressure