9-2. FAILURE MODE RECALL FUNCTION

Outline of the function

This air conditioner can memorize the abnormal condition which has occurred once.

Even though LED indication listed on the troubleshooting check table (9-4.) disappears, the memorized failure details can be recalled.

This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.

1. Flow chart of failure mode recall function for the indoor/outdoor unit

Operational procedure

The cause of abnormality cannot be found because the abnormality doesn't recur.

Setting up the failure mode recall function

Turn ON the power supply. <Preparation of the remote controller>

While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button.

First, release RESET button.

And release the other two buttons after all LCD in operation display section of the remote controller is displayed after 3 seconds.

Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1

1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.

Does the POWER lamp on the indoor unit blink at

 

the interval of 0.5 seconds?

 

Blinks: Either indoor or outdoor unit is abnormal.

No

Beep is emitted at the same timing as the

(OFF)

blinking of POWER lamp. 2

 

 

 

Yes

 

 

 

 

Judgment of indoor/outdoor abnormality

 

(Blinks)

 

 

 

Before blinking, does POWER lamp stay ON for 3 seconds?

Stays ON for 3 seconds (without beep): Yes The outdoor unit is abnormal.

No

The indoor unit is abnormal.

Check the blinking pattern, and confirm the abnormal point with the indoor unit failure mode table. (Refer to 9-2.2)

Make sure to check at least two consecutive blinking cycles. 2

Indoor unit is normal.

But the outdoor unit might be abnormal because there are some abnor- malities that can't be recalled with this way.

Confirm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function.

The outdoor unit is abnormal.

Check the blinking pattern, and confirm the abnormal point with the outdoor unit failure mode table. (Refer to outdoor unit service manual.) Make sure to check at least two consecutive blinking cycles. 3

Releasing the failure mode recall function

Release the failure mode recall function by the following procedures.

Turn OFF the power supply and turn it ON again.

Press RESET button of the remote controller.

Repair the defective parts.

Deleting the memorized abnormal condition

After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above.

Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.

Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.

NOTE: 1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.

2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.

2. Blinking pattern when the indoor unit is abnormal:

 

 

 

 

Blinking at 0.5-

 

 

 

 

 

 

 

 

Blinking at 0.5-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5-second OFF

second interval

2.5-second OFF second interval

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Beeps

 

 

 

 

 

 

 

 

 

 

 

 

 

Beeps

 

 

 

Beeps

 

 

 

 

 

 

 

 

 

 

 

 

 

Repeated cycle

 

 

 

 

 

Repeated cycle

Repeated cycle

 

 

 

 

 

 

 

 

 

 

3.Blinking pattern when the outdoor unit is abnormal:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blinking at 0.5-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blinking at 0.5-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5-second OFF

 

 

3-second ON

 

 

second interval

 

 

 

2.5-second OFF

3-second ON

 

second interval

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No beep

 

 

 

 

 

Beeps

 

 

 

 

 

 

 

 

No beep

 

 

 

Beeps

 

 

 

 

 

 

Repeated cycle

 

 

 

 

 

 

 

 

Repeated cycle

 

 

 

 

 

 

 

 

 

Repeated cycle

23

Image 23
Contents MSZ-FD09NA MSZ-FD12NA Specification has been corrected New model Part Names and Functions AccessoriesIndoor model Power supply Phase, Hz 208/230Weight External finish Remote controllerOutlet AIR Speed and Coverage Range Operating RangeAir out Outlines and DimensionsUnit inch AirWiring Diagram Refrigerant flow in cooling Refrigerant flow in heating Refrigerant System DiagramUnitinch P.C. Board Modification for Individual Operation Service FunctionsTimer Short Mode How to modify the remote controller P.C. boardOperation How to release Auto Restart FunctionAuto Restart Function Lamp blinks in abnormal condition Microprocessor ControlRefer to Lamp lights during operationHeat Operation Cool OperationDRY Operation Outdoor Unit MXZ series Auto Change Over ··· Auto Mode OperationMode selection Auto Vane OperationFeet, set the horizontal DirectionVertical vane Enlarged view of i-see Sensor Area SettingSee Control Operation See SensorLighted Not lighted DaytimeNighttime Cold area Center ····· Operation and operating range Program Timer EMERGENCY/TEST Operation Minute Time Delay OperationChanging temperature indication F/C How to replace batteries TroubleshootingBefore troubleshooting, check the following Lead wiring Housing point Troubleshooting procedureOFF Failure Mode Recall FunctionPower Indoor unit failure mode tableInstruction of Troubleshooting Lighted Blinking Troubleshooting Check TableArea R Power Trouble Criterion of Main Parts MSZ-FD09NAMSZ-FD12NA Check of indoor fan motor Troubleshooting FlowPage Replace the horizontal vane motor, How to check miswiring and serial signal error Electromagnetic noise enters into TV sets or radios SW P.C. Board Test Point Diagram and VoltageIndoor electronic control P.C. board Power monitor receiver P.C. board Monitor P.C. board Removing the panel Photo Disassembly InstructionsOpen the rear cover of the power monitor receiver P.C Operating Procedure PhotosCorrect position Removing the nozzle assemblyRemoving the electrical box Photo Photo Removing the vertical vane motor unitRemoving the indoor fan motor and the line flow fan Photo Removing the horizontal vane motor PhotoMade in Japan