Mitsubishi Electronics MSZ-FD09NA Electromagnetic noise enters into TV sets or radios

Page 33

E Electromagnetic noise enters into TV sets or radios

Is the unit grounded?

Yes

Is the distance between the antennas and the indoor unit within 9.91 ft., or is the distance between the antennas and the outdoor unit within 9.91 ft.?

No

Is the distance between the TV sets or radios and the indoor unit within 3.28 ft., or is the distance between the TV sets or radios and the outdoor unit within 9.91 ft.?

No

Are the antennas damaged? Is the coaxial cable damaged?

Is there any poor contact in the anten- na wiring?

No

Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?

No

No

Yes

Yes

Yes

Yes

Ground the unit.

Extend the distance between the antennas and the indoor unit, and/or the antennas and the

outdoor unit.

Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or

radios and the outdoor unit.

Replace or repair the antenna.

Replace or repair the coaxial cable.

Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wir-

ing of the antennas.

Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength or the installation condition (combination of specific conditions such as antennas or wiring).

Check the followings before asking for service.

1.Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)

2.Channel, frequency, broadcast station affected by the electromagnetic noise

3.Channel, frequency, broadcast station unaffected by the electromagnetic noise

4.Layout of ;

indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, re- ceiver

5.Electric field intensity of the broadcast station affected by the electromagnetic noise

6.Presence or absence of amplifier such as booster

7.Operation condition of air conditioner when the electromagnetic noise enters in

1)Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.

2)Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.

3)After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.

4)Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.

33

Image 33
Contents MSZ-FD09NA MSZ-FD12NA Specification has been corrected New model Part Names and Functions AccessoriesWeight External finish Power supply Phase, Hz 208/230Remote controller Indoor modelOutlet AIR Speed and Coverage Range Operating RangeUnit inch Outlines and DimensionsAir Air outWiring Diagram Refrigerant System Diagram UnitinchRefrigerant flow in cooling Refrigerant flow in heating Timer Short Mode Service FunctionsHow to modify the remote controller P.C. board P.C. Board Modification for Individual OperationHow to release Auto Restart Function Auto Restart FunctionOperation Refer to Microprocessor ControlLamp lights during operation Lamp blinks in abnormal conditionCool Operation DRY OperationHeat Operation Mode selection Auto Change Over ··· Auto Mode OperationAuto Vane Operation Outdoor Unit MXZ seriesFeet, set the horizontal DirectionVertical vane See Control Operation Area SettingSee Sensor Enlarged view of i-see SensorDaytime Nighttime Cold areaLighted Not lighted Center ····· Operation and operating rangeProgram Timer Minute Time Delay Operation Changing temperature indication F/CEMERGENCY/TEST Operation Before troubleshooting, check the following TroubleshootingLead wiring Housing point Troubleshooting procedure How to replace batteriesOFF Failure Mode Recall FunctionPower Indoor unit failure mode tableInstruction of Troubleshooting Lighted Blinking Troubleshooting Check TableArea R Power Trouble Criterion of Main Parts MSZ-FD09NAMSZ-FD12NA Check of indoor fan motor Troubleshooting FlowPage Replace the horizontal vane motor, How to check miswiring and serial signal error Electromagnetic noise enters into TV sets or radios Test Point Diagram and Voltage Indoor electronic control P.C. boardSW P.C. Board Power monitor receiver P.C. board Monitor P.C. board Removing the panel Photo Disassembly InstructionsOpen the rear cover of the power monitor receiver P.C Operating Procedure PhotosRemoving the electrical box Photo Removing the nozzle assemblyPhoto Removing the vertical vane motor unit Correct positionRemoving the indoor fan motor and the line flow fan Photo Removing the horizontal vane motor PhotoMade in Japan