Mitsubishi Electronics MSZ-FD09NA Operating Range, Outlet AIR Speed and Coverage Range

Page 6

3-1. OPERATING RANGE

(1) POWER SUPPLY

 

Rated voltage

 

Guaranteed Voltage

 

 

 

 

 

 

 

 

208/230 V

Min.187 V 208 V 230 V Max.253 V

Indoor unit

1 phase

 

 

 

 

 

 

 

 

 

 

 

60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

(2) OPERATION

Mode

Condition

 

 

Intake air temperature (°F)

 

 

Indoor

 

 

Outdoor

 

 

DB

 

WB

DB

 

WB

 

Standard temperature

80

 

67

95

 

Cooling

Maximum temperature

90

 

73

115

 

Minimum temperature

67

 

57

14

 

 

 

 

 

Maximum humidity

78

%

 

 

Heating

Standard temperature

70

 

60

47

 

43

Maximum temperature

80

 

67

75

 

65

 

Minimum temperature

70

 

60

14

 

13

3-2. OUTLET AIR SPEED AND COVERAGE RANGE

Model

Mode

Function

Airflow

Air speed

Coverage

(CFM)

(ft./sec.)

range (ft.)

 

 

 

 

HEAT

Dry

381

19.2

27.7

MSZ-FD09NA

COOL

Dry

339

17.1

24.7

 

Wet

307

15.5

22.4

 

 

 

HEAT

Dry

420

21.2

30.4

MSZ-FD12NA

COOL

Dry

381

19.2

27.7

 

Wet

350

17.6

25.4

 

 

The air coverage range is the figure up to the position where the air speed is 1 ft./sec., when air is blown out horizon- tally from the unit properly at the High speed position.

The coverage range should be used only as a general guideline since it var- ies according to the size of the room and furniture arranged inside the room.

6

Image 6
Contents MSZ-FD09NA MSZ-FD12NA Specification has been corrected New model Accessories Part Names and FunctionsRemote controller Power supply Phase, Hz 208/230Weight External finish Indoor modelOperating Range Outlet AIR Speed and Coverage RangeAir Outlines and DimensionsUnit inch Air outWiring Diagram Refrigerant System Diagram UnitinchRefrigerant flow in cooling Refrigerant flow in heating How to modify the remote controller P.C. board Service FunctionsTimer Short Mode P.C. Board Modification for Individual OperationHow to release Auto Restart Function Auto Restart FunctionOperation Lamp lights during operation Microprocessor ControlRefer to Lamp blinks in abnormal conditionCool Operation DRY OperationHeat Operation Auto Vane Operation Auto Change Over ··· Auto Mode OperationMode selection Outdoor Unit MXZ seriesDirection Feet, set the horizontalVertical vane See Sensor Area SettingSee Control Operation Enlarged view of i-see SensorDaytime Nighttime Cold areaLighted Not lighted Operation and operating range Center ·····Program Timer Minute Time Delay Operation Changing temperature indication F/CEMERGENCY/TEST Operation Lead wiring Housing point Troubleshooting procedure TroubleshootingBefore troubleshooting, check the following How to replace batteriesFailure Mode Recall Function OFFIndoor unit failure mode table PowerInstruction of Troubleshooting Troubleshooting Check Table Lighted BlinkingArea R Power Trouble Criterion of Main Parts MSZ-FD09NAMSZ-FD12NA Troubleshooting Flow Check of indoor fan motorPage Replace the horizontal vane motor, How to check miswiring and serial signal error Electromagnetic noise enters into TV sets or radios Test Point Diagram and Voltage Indoor electronic control P.C. boardSW P.C. Board Power monitor receiver P.C. board Monitor P.C. board Disassembly Instructions Removing the panel PhotoOperating Procedure Photos Open the rear cover of the power monitor receiver P.CPhoto Removing the vertical vane motor unit Removing the nozzle assemblyRemoving the electrical box Photo Correct positionRemoving the horizontal vane motor Photo Removing the indoor fan motor and the line flow fan PhotoMade in Japan