Mitsubishi Electronics PAC-YG60MCA instruction manual Switch List, Supported Function

Page 11

9Switch List

SW

 

Supported

Function

OFF

ON

Remark

 

Channel

 

 

 

 

 

 

 

 

 

 

 

 

 

SW01

1

Channel 1

Use of input contact

No

Yes

Set whether to use the Channel 1 input.

 

2

Channel 2

Use of input contact

No

Yes

Set whether to use the Channel 2 input.

 

3

Channel 3

Use of input contact

No

Yes

Set whether to use the Channel 3 input.

 

4

Channel 4

Use of input contact

No

Yes

Set whether to use the Channel 4 input.

 

5

Unused

 

 

 

Set to OFF

 

6

Unused

 

 

 

Set to OFF

 

7

Unused

 

 

 

Set to OFF

 

8

Unused

 

 

 

Set to OFF

SW02

1

 

Pulse weight value setting:

SW02-1,

SW02-2

 

 

 

SC setting (*1):

OFF

OFF

 

 

 

Channel 1

× 0.1:

OFF

ON

Set 1 pulse of the meter connected to channel 1.

 

 

 

2

 

× 1:

ON

OFF

 

 

 

× 10:

ON

ON

 

 

 

 

 

 

3

 

Pulse weight value setting:

SW02-3,

SW02-4

 

 

 

SC setting (*1):

OFF

OFF

 

 

 

Channel 2

× 0.1:

OFF

ON

Set 1 pulse of the meter connected to channel 2.

 

 

 

4

 

× 1:

ON

OFF

 

 

 

× 10:

ON

ON

 

 

 

 

 

 

5

 

Pulse weight value setting:

SW02-5,

SW02-6

 

 

 

SC setting (*1):

OFF

OFF

 

 

 

Channel 3

× 0.1:

OFF

ON

Set 1 pulse of the meter connected to channel 3.

 

 

 

6

 

× 1:

ON

OFF

 

 

 

× 10:

ON

ON

 

 

 

 

 

 

7

 

Pulse weight value setting:

SW02-7,

SW02-8

 

 

 

SC setting (*1):

OFF

OFF

 

 

 

Channel 4

× 0.1:

OFF

ON

Set 1 pulse of the meter connected to channel 4.

 

 

 

8

 

× 1:

ON

OFF

 

 

 

× 10:

ON

ON

 

 

 

 

 

SW03

1

Unused

 

 

 

Set to OFF

 

2

Unused

 

 

 

Set to OFF

 

3

Unused

 

 

 

Set to OFF

 

4

Unused

 

 

 

Set to OFF

 

5

Unused

 

 

 

Set to OFF

 

6

Unused

 

 

 

Set to OFF

 

7

Unused

 

 

 

Set to OFF

 

8

Unused

 

 

 

Set to OFF

SW06

 

 

 

(Address 10s) 0 to 9 (decimal)

An address from 01 to 50 can be set.

 

 

M-NET address

 

 

 

Set an address that is not the same as that of

SW07

 

 

(Address 1s) 0 to 9 (decimal)

 

 

 

another unit.

SW08

 

 

 

 

 

Only enabled during communication error status

 

 

Communication error status display (error code

Change the switch to ON once

display.

 

1

display)

 

* The communication error status display is

 

 

and then return it to OFF.

 

 

Temporary mask setting

masked for 10 seconds and the contact input

 

 

 

 

 

 

 

 

 

 

status is displayed.

 

2

Unused

 

 

 

Set to OFF

 

3

Unused

 

 

 

Set to OFF

 

4

Unused

 

 

 

Set to OFF

 

5

Unused

 

 

 

Set to OFF

 

6

Unused

 

 

 

Set to OFF

SW09

1

Unused

 

 

 

Set to OFF

 

2

Unused

 

 

 

Set to OFF

Set the dip switches for function selection according to the system to be used.

At the time of shipment, all dip switches are set to OFF and the M-NET address is set to 01.

*1: When using a system controller (G(B)-50A or TG-2000A), select the "SC setting" and set the pulse weight value settings from a system controller. If set to another setting, this dip switch setting is prioritized even when set from a system controller.

*2: The pulse unit of the watt-hour meter being used should be 1 kWh/pulse or less. Note that the apportioning error will increase if a watt-hour meter with large pulse unit is used.

10

Image 11 Contents
PI controller Device Capabilities Safety PrecautionsExternal View Specifications Product SpecificationsConfirmation of Parts Restrictions Example of System ConfigurationInstallation Method Parts to be Procured Locally Installation Procedure Wiring in the diagram has been simplified Wiring Method Names of PartsEquivalent to one ME Remote Controller Connecting the Power Line and M-NET Transmission LineConnecting the Signal Lines Initial Setting Procedure Supported Function Switch ListCommunication Error Status Display Display ContentDisplay Content List Test Run Precautions for ExpansionPage Page WT04973X01