6Installation Method
6-1. Parts to be Procured Locally
Prepare the following parts to install this device.
Required Part |
| Specification |
|
|
|
|
|
Unit fixing screws | M4 screw × 4 |
|
|
| Power source: 24 VDC 0.2 A (Minimum loading), SELV circuit, power line with grounding terminal | ||
| Ripple noise: Lower than 200 |
| |
Power supply for this | Compatible specification |
| |
Authorized or CE marked products |
| ||
unit |
| ||
Subject to regulations: - IEC60950 (or EN60950) |
| ||
|
| ||
|
| - CISPR22/24 (or EN55022/24) |
|
|
| - | |
Power line | Use a sheathed vinyl cord or cable. |
| |
At least 0.75 mm² (AWG18) |
| ||
|
| ||
| Type of the cable: Sheathed vinyl cords or cable which comply with the following specifications or equivalent. | ||
| • CPEV Φ1.2 mm to Φ1.6 mm • CVVS 1.25 mm² to 2 mm² (AWG16 to 14) | ||
* CPEV: PE insulated PVC jacketed shielded communication cable |
| ||
line | * CVVS: PVC insulated PVC jacketed shielded control cable |
| |
PE: Polyethylene PVC: Polyvinyl choloride |
| ||
| Power needs to be supplied to the | ||
| power supply unit for the transmission line. |
| |
| Shows the size of the electric wire (copper wire) that is adapted to the terminal block of this device. | ||
Signal lines | Electric wire size ········· (1) Solid wire: Φ0.65 mm (AWG21) - Φ1.2 mm (AWG16) | ||
| (2) Stranded wire: 0.75 mm² (AWG18) - 1.25 mm² (AWG16) | ||
|
| ||
|
| Single strand: At least Φ0.18 mm | |
[Parts to be Purchased Separately] |
|
| |
|
|
|
|
Name | Model | Application | Remark |
|
|
|
|
Power supply unit |
| Power supply to the | This is not required when power is to be |
|
|
| supplied from an outdoor unit. |
[Recommended Pulse Specifications]
Prepare a measuring instrument that measures the type of pulse signals indicated in table below.
Type |
| Specifications |
|
|
|
|
|
|
|
|
|
|
|
Output pulse relay | Semiconductor relay method |
|
|
|
| |
method |
|
|
|
| ||
|
|
|
|
|
| |
| 100 ~ 300 ms (100 ms and above) | ON |
|
|
| |
| Choose an instrument that outputs |
|
|
| ||
Output pulse width |
|
|
|
| ||
point pulse per each pulse output. |
|
|
|
| ||
|
|
| 100 ~ 300 ms | |||
|
|
|
|
| ||
|
|
|
|
|
| |
|
|
|
|
| ||
| Water meter: m3/pulse |
|
|
|
| |
Pulse unit | Gas meter: | m3/pulse |
|
|
|
|
| Calorimeter: | MJ/pulse |
|
|
|
|
* Except for the