Mitsubishi Electronics PAR-FL32MA installation manual Display of individually set items

Page 6

<Display of individually set items>

Display will change with the change in the setting number.

No. of Fan speeds 1

01: 4 speeds

02: 3 speeds

03: 2 speeds

04: Fixed speed

Louver swing 2

01: Disabled

02: Enabled

No display

 

Vane 3

 

01: Adjustable vane/Auto swing enabled

02: Adjustable vane/Auto swing disabled

Operation mode 4

01: Heat pump model

02: Cooling-only model

COOL

COOL

DRY

DRY

AUTO

 

FAN

FAN

HEAT

 

 

5

1

8

4

CHECK

TESTRUN

6

 

 

MODEL SELECT

7

 

 

 

9

2

 

 

 

 

NOT AVAILABLE

 

03: Fixed

3

 

 

No display

 

 

03: K-control heat pump model

04: Not to be selected

 

COOL

 

 

 

DRY

 

 

 

AUTO

 

 

 

HEAT

 

 

 

05: Cooling-only model (without Dry mode)

06: Heat pump model (without Dry mode)

COOL

 

COOL

 

 

 

DRY

 

 

 

AUTO

 

FAN

 

FAN

 

07: Heat pump model (without Dry or Auto modes)

08: K-control heat pump model

COOL

 

COOL

 

 

 

DRY

 

FAN

 

FAN

 

HEAT

 

HEAT

 

Auto fan speed control 5

Preset temperature 6

 

01: Disabled

02: Enabled

01: Available

02: Unavailable

No display

 

°F

No display

 

 

°C

 

 

 

Temperature display in Centigrade and Fahrenheit (Displayed in the hour section of the clock) 7

01: °C02: °F

Pair No. (Displayed in the preset temperature window) 8

0 ~ 9

Model (Displayed in the minute section of the clock) 9

01: Standard (2 °F)

02: Standard (1 °F)

03: SLIM middle temperature

04: CITY MULTI middle temperature

05: Low temperature

06: RAC

Unless this setting is set to “01,” preset temperature can be changed in 1 °F increments when “temperature display in Fahrenheit” is selected.

By setting the model type, preset temperature range will be defined as in the table below.

Setting

Model

Centigrade/

Setting increments

Cool/Dry

Heat

Auto

Fahrenheit

 

 

 

 

 

 

 

01

Standard 2 °F model

Both SLIM and CITY MULTI

Centigrade

1 °C

19 ~ 30 °C

17 ~ 28 °C

19 ~ 28 °C

models

Fahrenheit

2 °F

67 ~ 87 °F

63 ~ 83 °F

67 ~ 83 °F

 

 

02

Standard 1 °F model

Both SLIM and CITY MULTI

Centigrade

1 °C

19 ~ 30 °C

17 ~ 28 °C

19 ~ 28 °C

models

Fahrenheit

1 °F

67 ~ 87 °F

63 ~ 83 °F

67 ~ 83 °F

 

 

03

 

SLIM model

Centigrade

1 °C

14 ~ 30 °C

14 ~ 28 °C

Middle

Fahrenheit

1 °F

57 ~ 87 °F

57 ~ 83 °F

 

 

04

temperature model

CITY MULTI model

Centigrade

1 °C

14 ~ 30 °C

17 ~ 28 °C

 

Fahrenheit

1 °F

57 ~ 87 °F

63 ~ 83 °F

 

 

 

05

Low temperature model

Both SLIM and CITY MULTI

Centigrade

1 °C

8 ~ 30 °C

8 ~ 28 °C

models

Fahrenheit

1 °F

46 ~ 87 °F

46 ~ 83 °F

 

 

06

RAC model

Centigrade

1 °C

 

16 ~ 31 °C

 

Fahrenheit

1 °F

 

61 ~ 88 °F

 

 

 

 

 

 

6

Image 6
Contents Safety Precautions Confirming the Supplied PartsModel setting must be made to control indoor units InstallationModel Setting Cool/Dry/Auto/Fan/HeatSetting Procedures Model number Louver Display of individually set items Pair Number Setting Test Run MethodOperation Lamp Display and Buzzer Self-Diagnosis Case of a problemOperating Procedures Making a self-diagnosis