Whirlpool RH4900 SERIES, RH4700 SERIES Venting requirements, Now start, Vented installation

Page 3

Venting requirements

Horizontal wall venting

 

Now start...

Venting system must terminate to the outside.

Do not terminate the vent in an attic or other enclosed space.

Do not use four-inch laundry-type wall caps.

Do not use plastic vent.

Vent system needed for installation is not included. Wall or roof caps used must have backdraft damper.

Determine which outside venting method needs to be used. NOTE: If a non-vented (recirculating) installation is desired, follow instructions on Panel D.

The length of the vent system and number of elbows should be kept to a minimum to provide efficient performance. The size of the vent system should be uniform. Do Not install two elbows together. Use duct tape to seal all joints in the vent system. Vent system can terminate either through the roof or wall. Use caulking to seal exterior wall or roof opening around exhaust hood. For the most efficient and quiet operation, it is recommended that the range be vented vertically through the roof through 7" round vent system.

Figures 1-4 show common venting methods and what types of materials are needed.

Vertical roof venting

roof cap

7" round

through roof

damper located

as far from hood

as possible

66"

Figure 1

Vertical roof venting

roof cap

3-1/4" x 10" through the roof

3-1/4" x 10" damper

3-1/4" x 10"

through the wall

wall cap

66"

Figure 3

roof cap

7" min. diameter

wall cap

round vent

 

elbows

 

3-1/4" x 10" to round vent transition

Figure 4

Recommended vent length

Use 3-1/4" x 10" or 7" vent with a maximum length of 26 feet for vent system. For best performance, use no more than three 90° elbows. To calculate the length of system you need, add the equivalent feet for each vent piece used in the system. See the following examples.

3-1/4" x 10" vent system

3-1/4" x 10"

 

 

6 ft.

 

 

 

 

wall cap

 

 

 

 

 

elbow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum length

= 26 feet

 

 

 

 

1 - 90° elbow

=

5

ft.

 

2 ft.

 

 

 

8 feet straight

=

8

ft.

 

 

 

1 - wall cap

=

0

ft.

 

 

 

Length of 3-1/4" x

 

 

 

 

 

 

10" system

= 13

ft.

Recommended standard fittings

3-1/4" x 10" 90°

3-1/4" x 10" flat

3-1/4" x 10" wall

elbow = 5 ft.

elbow = 12 ft.

cap = 0 ft.

 

 

 

7" vent system

With range hood in kitchen.

Slide cardboard or hardboard under range before moving range across floor to prevent damaging floor covering.

Cover countertop, cooktop or set-in range with a thick, protective covering to prevent damaging countertop.

1.Disconnect and move freestanding range from cabinet opening to provide easier access to upper cabinet and rear wall. Put a thick, protective covering over cooktop, set-in range or countertop to protect from damage or dirt.

2.Determine which venting method (roof or wall venting or non-venting) you need to use. This range hood is shipped for non-vented installation.

If non-venting (recirculating) installation is desired, follow instructions on Panel D.

Vented installation

3.

Remove screws from vent baffle on

top of range hood. Remove vent baffle.

4.

Turn vent baffle and reinsert in slot in top of range hood so that the word “Vented” is facing up. Fasten vent baffle with screws.

vent knockouts

66"

Figure 2

90° elbow

3-1/4" x 10" to 7" transition

6 ft.

2 ft.

Maximum length

1 - transition

2 - 90° elbows

1 - wall cap

8 feet straight

wall cap

=26 feet

=4.5 ft.

=10 ft.

=0 ft.

=8 ft.

5.

wiring

knockouts

 

Remove knockout from the wiring opening (top or rear) to be used.

For rectangular venting, remove only the

3-1/4" x 10" rectangular opening knockout.

For round ventwork venting through roof, remove both opening knockouts.

Length of 7" system = 22.5 ft.

Recommended standard fittings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-1/4" x 10" to

3-1/4" x 10" to 7"

90° elbow = 5 ft.

 

7" = 4.5 ft.

90° elbow = 5 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45° elbow = 2.5 ft.

7" wall cap = 0 ft.

terminal box cover

6.

Remove terminal box cover from range hood.

Panel B

Image 3 Contents
RH4900 Series shown Installation Instructions and Use and CareElectrical requirements Product dimensionsTools and materials needed for installation Before you startVented installation Venting requirementsNow start Panel C Numbers correspond to stepsNon-vented installation CongratulationsPanel D Use & Care Information Operation Range hoodCare of range hood If you need Assistance If you need ServiceWhirlpool Range Hood Warranty If range hood does Not operate